| Weight | 0.113 KG / psc. |
| Commodity number | 90303370 |
| Country of origin | DE |
| Dimensions (WxHxD) | 22.5x78x102 mm |
| EAN code | 4016779837200 |
| Product group | EB |
| cn8 | 8536 49 00 |
| eclass | V11.0 : 27370805 |
| etim 7 | EC002613 - Extension module for motor management device |
| etim 8 | EC002613 - Extension module for motor management device |
| standards | CAN/CSA C22.2 No.14IEC/EN 60947-1IEC/EN 60947-5-1IEC/EN 61131-2UL 508 |
| power loss | Approximately 0.6 W |
| rohs status | Following EU Directive 2011/65/EU |
| suitable for | UMC100-FBPUMC100.3 |
| analog inputs | 3 |
| terminal type | Screw Terminals |
| weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| gl certificate | https://library.abb.com/d/1SAA962005-0401 |
| weee b2c / b2b | Business To Business |
| abs certificate | https://library.abb.com/d/17-HG1610225-PDA |
| dnv certificate | https://library.abb.com/d/DNV_E-13261 |
| number of poles | 3 |
| atex certificate | https://library.abb.com/d/No |
| pollution degree | 3 |
| rohs information | https://library.abb.com/d/1SVD981039 |
| culus certificate | https://library.abb.com/d/cULus_20120412_E48139 |
| mounting position | Any |
| tightening torque | Auxiliary Circuit 0.22 N·mControl Circuit 0.6 ... 0.8 N·m |
| dnv gl certificate | https://library.abb.com/d/TAA000015X |
| e-number (finland) | 3709072 |
| eplan catalog tree | Electrical engineering / Protection devices / Motor overload switch |
| input voltage type | AC |
| connecting capacity | 1x 0.75-2.5 mm2 |
| rated frequency (f) | Main Circuit 50 / 60 Hz |
| degree of protection | IP20 |
| mounting on din rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| phase loss sensitive | Yes |
| wire stripping length | 7 mm |
| suitable for isolation | No |
| ambient air temperature | Storage -25 ... +70 °COperation 0 ... +60 °C |
| recommended screw driver | Pozidriv 1 |
| rated operational voltage | Main Circuit 690 V ACAuxiliary Circuit 12 ... 250 V AC/DC |
| connecting capacity ul/csa | Flexible with Ferrule 1x 18-14 AWGFlexible 1x 18-14 AWGRigid 1x 20-12 AWG |
| object classification code | B |
| suitable for product class | Universal Motor Controllers |
| rated insulation voltage (ui) | 690 V |
| declaration of conformity - ce | https://library.abb.com/d/1SVD981039 |
| number of digital output relays | 1 |
| maximum operating voltage ul/csa | Main Circuit 600 V AC |
| regulatory compliance mark (rcm) | No |
| data sheet, technical information | https://library.abb.com/d/2CDC135013D0202 |
| rated control supply voltage (us) | 24 V DC |
| rated operational current ac-15 (ie) | (240 V) 1.5 A |
| rated impulse withstand voltage (uimp) | Main Circuit 8 kVAuxiliary Circuit 4 kV |
| type of low voltage distribution system | TN |
| resistance to shock acc. to iec 60068-2-27 | 11 ms Pulse 150 m/s2 |
| resistance to vibrations acc. to iec 60068-2-6 | 5g / 3 ... 150 Hz |