ABB

1SAM340010R1006

Product type: MS132-1.6KT

MS132-1.6KT Circuit Breaker for Primary Transformer Protection 1.0 ... 1.6 A

RoHS Compliant

Description

The circuit breaker for transformer protection MS132-1.6KT is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 1.6 A with Push-In Spring terminals. It allows fuseless protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips and terminal spacers are available as accessory. MS132-1.6KT
  • Low Voltage Products and Systems
  • Control Products
  • Manual Motor Starters
  • Manual Motor Starters for Special Use
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.298 KG / psc.
Commodity number85362010
Country of originDE
Dimensions (WxHxD)50x82x117 mm
EAN code4013614535161
Product group
eclass V11.0 : 27370409
etim 5 EC000228 - Power circuit-breaker for trafo/generator/installation prot.
etim 6 EC000228 - Power circuit-breaker for trafo/generator/installation prot.
etim 7 EC000228 - Power circuit-breaker for trafo/generator/installation protection
etim 8 EC000228 - Power circuit-breaker for trafo/generator/installation protection
unspsc 39121601
standards IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1
power loss at Rated Operating Conditions per Pole 0.6 ... 1.6 W
rohs status Following EU Directive 2011/65/EU
actuator type Rotary Handle
setting range 1.0 ... 1.6 A
terminal type Push-in Spring Terminals
kc certificate https://library.abb.com/d/1SAA963002-1502
cqc certificate https://library.abb.com/d/CQC2017010307034621
cul certificate https://library.abb.com/d/cUL_E137861
cur certificate https://library.abb.com/d/cUL_E137861
marketing video https://library.abb.com/d/9AKK107991A4712, https://library.abb.com/d/2CDC131153V0201
number of poles 3
pollution degree 3
rmrs certificate https://library.abb.com/d/1SAA918000-0704
rohs information https://library.abb.com/d/1SAD938508-0188
culus certificate https://library.abb.com/d/cUL_E137861
locked rotor amps (120 V AC) Single Phase 9.6 A(220 ... 240 V AC) Single Phase 9.6 A
mounting position 1 ... 6
e-number (finland) 3709083
i2t characteristic https://library.abb.com/d/1SAM300517F0001
rated frequency (f) Main Circuit 50 HzMain Circuit 60 Hz
degree of protection Housing IP20Main Circuit Terminals IP20
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
electrical durability 50000 cycle
mechanical durability 100000 cycle
wire stripping length Main Circuit 12 mm
ambient air temperature Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
full load amps motor use (120 V AC) Single Phase 1.6 A(220 ... 240 V AC) Single Phase 1.6 A
horsepower rating ul/csa (220 ... 240 V AC) Single Phase 0.1 Hp
environmental information https://library.abb.com/d/1SAC200049H0009
minimum mounting distance Electrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 9 mmOther Device Same Type, Vertical 150 mm
rated operational voltage Main Circuit 690 V AC
object classification code F
contact position indication ON / OFF / TRIP
rated insulation voltage (ui) 690 V
declaration of conformity - ce https://library.abb.com/d/1SAD101100-3404
rated operational current (ie) 1.6 A
declaration of conformity - ccc https://library.abb.com/d/2020980307004600
connecting capacity main circuit Flexible with Ferrule 1/2x 0.5 ... 4 mm2Flexible with Insulated Ferrule 1x 0.5 ... 4 mm2Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm2Flexible 1/2x 0.75 ... 4 mm2Solid 1/2x 1 ... 2.5 mm2Stranded 1/2x 1 ... 6 mm2
declaration of conformity - ukca https://library.abb.com/d/1SAD201100-3404
maximum operating voltage ul/csa Main Circuit 600 V AC
data sheet, technical information https://library.abb.com/d/2CDC131058D0201
time-current characteristic curve https://library.abb.com/d/1SAM300535F0006
idea granular category code (igcc) 4813 >> Circuit breakers
short-circuit current rating (sccr) Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
ambient air temperature compensation Yes
maximum operating altitude permissible 2000 m
rated impulse withstand voltage (uimp) Main Circuit 6 kV
connecting capacity main circuit ul/csa Stranded 1/2x 18-10 AWGStranded 1x 8 AWG
resistance to shock acc. to iec 60068-2-27 11 ms Pulse 25g
conventional free-air thermal current (ith) Main Circuit 1.6 A
resistance to vibrations acc. to iec 60068-2-6 5g / 3 ... 150 Hz
rated service short-circuit breaking capacity (ics) (230 V AC) 100 kA(400 V AC) 100 kA
rated ultimate short-circuit breaking capacity (icu) (400 V AC) 100 kA
rated instantaneous short-circuit current setting (ii) 32 A