Product type: MS132-6.3KT
MS132-6.3KT Circuit Breaker for Primary Transformer Protection 4.0 ... 6.3 A
RoHS Compliant
Description
| Thomas Hoffmann |
| +49 305 201 4443 |
| sales@zwodltd.com |
| Price: Please send request |
| Request Lead Time: app. 1 Day |
| Delivery Time: app. 6-9 Weeks Estimated delivery time to our warehouse in Berlin |
| Delivery Terms: FCA Berlin individually for each client according to INCOM TERMS 2025 |
| Product Attribute | Attribute Value |
|---|---|
| Weight | 0.289 KG / psc. |
| Commodity number | 85362010 |
| Country of origin | DE |
| Dimensions (WxHxD) | 50x82x117 mm |
| EAN code | 4013614535192 |
| Product group | |
| eclass | V11.0 : 27370409 |
| etim 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
| etim 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
| etim 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| etim 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| unspsc | 39121601 |
| standards | IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1 |
| power loss | at Rated Operating Conditions per Pole 0.7 ... 1.8 W |
| rohs status | Following EU Directive 2011/65/EU |
| actuator type | Rotary Handle |
| setting range | 4.0 ... 6.3 A |
| terminal type | Push-in Spring Terminals |
| kc certificate | https://library.abb.com/d/1SAA963002-1502 |
| cqc certificate | https://library.abb.com/d/CQC2017010307034621 |
| cul certificate | https://library.abb.com/d/cUL_E137861 |
| cur certificate | https://library.abb.com/d/cUL_E137861 |
| marketing video | https://library.abb.com/d/9AKK107991A4712, https://library.abb.com/d/2CDC131153V0201 |
| number of poles | 3 |
| pollution degree | 3 |
| rmrs certificate | https://library.abb.com/d/1SAA918000-0704 |
| rohs information | https://library.abb.com/d/1SAD938508-0188 |
| culus certificate | https://library.abb.com/d/cUL_E137861 |
| locked rotor amps | (120 V AC) Single Phase 37.8 A(220 ... 240 V AC) Single Phase 37.8 A |
| mounting position | 1 ... 6 |
| e-number (finland) | 3709086 |
| i2t characteristic | https://library.abb.com/d/1SAM300517F0001 |
| rated frequency (f) | Main Circuit 50 HzMain Circuit 60 Hz |
| degree of protection | Housing IP20Main Circuit Terminals IP20 |
| mounting on din rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| electrical durability | 50000 cycle |
| mechanical durability | 100000 cycle |
| wire stripping length | Main Circuit 12 mm |
| ambient air temperature | Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C |
| full load amps motor use | (120 V AC) Single Phase 6.3 A(220 ... 240 V AC) Single Phase 6.3 A |
| horsepower rating ul/csa | (120 V AC) Single Phase 0.25 Hp(220 ... 240 V AC) Single Phase 0.5 Hp |
| environmental information | https://library.abb.com/d/1SAC200049H0009 |
| minimum mounting distance | Electrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 9 mmOther Device Same Type, Vertical 150 mm |
| rated operational voltage | Main Circuit 690 V AC |
| object classification code | F |
| contact position indication | ON / OFF / TRIP |
| rated insulation voltage (ui) | 690 V |
| declaration of conformity - ce | https://library.abb.com/d/1SAD101100-3404 |
| rated operational current (ie) | 6.3 A |
| declaration of conformity - ccc | https://library.abb.com/d/2020980307004600 |
| connecting capacity main circuit | Flexible with Ferrule 1/2x 0.5 ... 4 mm2Flexible with Insulated Ferrule 1x 0.5 ... 4 mm2Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm2Flexible 1/2x 0.75 ... 4 mm2Solid 1/2x 1 ... 2.5 mm2Stranded 1/2x 1 ... 6 mm2 |
| declaration of conformity - ukca | https://library.abb.com/d/1SAD201100-3404 |
| maximum operating voltage ul/csa | Main Circuit 600 V AC |
| data sheet, technical information | https://library.abb.com/d/2CDC131058D0201 |
| time-current characteristic curve | https://library.abb.com/d/1SAM300535F0009 |
| idea granular category code (igcc) | 4813 >> Circuit breakers |
| short-circuit current rating (sccr) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA |
| ambient air temperature compensation | Yes |
| maximum operating altitude permissible | 2000 m |
| rated impulse withstand voltage (uimp) | Main Circuit 6 kV |
| connecting capacity main circuit ul/csa | Stranded 1/2x 18-10 AWGStranded 1x 8 AWG |
| resistance to shock acc. to iec 60068-2-27 | 11 ms Pulse 25g |
| conventional free-air thermal current (ith) | Main Circuit 6.3 A |
| resistance to vibrations acc. to iec 60068-2-6 | 5g / 3 ... 150 Hz |
| rated service short-circuit breaking capacity (ics) | (230 V AC) 100 kA(400 V AC) 100 kA |
| rated ultimate short-circuit breaking capacity (icu) | (400 V AC) 100 kA |
| rated instantaneous short-circuit current setting (ii) | 126 A |