ABB

1SAM350000R1010

Product type: MS132-10

MS132-10 Manual Motor Starter 6.3 ... 10 A

RoHS Compliant

Description

The MS132-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 10.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 VAC and trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory. MS132-10
  • Low Voltage Products and Systems
  • Circuit Breakers
  • Manual Motor Starters
  • Low Voltage Products and Systems
  • Control Products
  • Manual Motor Starters
  • Manual Motor Starters
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.265 KG / psc.
Commodity number85362010
Country of originDE
Dimensions (WxHxD)92x50x95 mm
EAN code4013614400100
Product group
eclass V11.0 : 27370401
etim 4 EC000074 - Motor protective circuit-breaker
etim 5 EC000074 - Motor protective circuit-breaker
etim 6 EC000074 - Motor protection circuit-breaker
etim 7 EC000074 - Motor protection circuit-breaker
etim 8 EC000074 - Motor protection circuit-breaker
unspsc 39121521
remarks UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx
standards IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1
power loss at Rated Operating Conditions per Pole 0.8 ... 2.0 W
rohs status Following EU Directive 2011/65/EU
actuator type Rotary Handle
setting range 6.3 ... 10 A
terminal type Screw Terminals
bv certificate https://library.abb.com/d/1SAA963001-0202
cb certificate https://library.abb.com/d/1SAA963002-2002
kc certificate https://library.abb.com/d/1SAA963002-1502
lr certificate https://library.abb.com/d/1SAA963001-0502
ul certificate https://library.abb.com/d/UL_E137861, https://library.abb.com/d/UL_E345003
abs certificate https://library.abb.com/d/1SAA963001-0101
cqc certificate https://library.abb.com/d/CQC2010010307387700, https://library.abb.com/d/CQC2019010307243864
cul certificate https://library.abb.com/d/cUL_E137861, https://library.abb.com/d/cUL_E345003
eac certificate https://library.abb.com/d/1SAA963000-2701
number of poles 3
atex certificate https://library.abb.com/d/1SAA963000-3902
pollution degree 3
rina certificate https://library.abb.com/d/1SAA963002-0802
rmrs certificate https://library.abb.com/d/1SAA918000-0704
rohs information https://library.abb.com/d/1SAD938511-0125
culus certificate https://library.abb.com/d/cUL_E137861
dimension diagram https://library.abb.com/d/1SAM300402F0001
e-number (sweden) 3112126
iecex certificate https://library.abb.com/d/1SAA963000-4001
locked rotor amps (200 V AC) Three Phase 57.5 A(208 V AC) Three Phase 55 A(220 ... 240 V AC) Three Phase 64 A(440 ... 480 V AC) Three Phase 46 A(550 ... 600 V AC) Three Phase 50.8 A
mounting position 1 ... 6
tightening torque Main Circuit 0.8 ... 1.2 N·m
dnv gl certificate https://library.abb.com/d/1SAA963001-0304
e-number (finland) 3705994
i2t characteristic https://library.abb.com/d/1SAM300507F0001, https://library.abb.com/d/1SAM300507F0003
rated frequency (f) Main Circuit 50 HzMain Circuit 60 Hz
degree of protection Housing IP20Main Circuit Terminals IP10
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
electrical durability 50000 cycle
mechanical durability 100000 cycle
wire stripping length Main Circuit 9 mm
ambient air temperature Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +60 °CStorage -50 ... +80 °C
full load amps motor use (200 V AC) Three Phase 7.8 A(208 V AC) Three Phase 7.5 A(220 ... 240 V AC) Three Phase 9.6 A(440 ... 480 V AC) Three Phase 7.6 A(550 ... 600 V AC) Three Phase 9 A
horsepower rating ul/csa (200 V AC) Three Phase 2 Hp(208 V AC) Three Phase 2 Hp(220 ... 240 V AC) Three Phase 3 Hp(440 ... 480 V AC) Three Phase 5 Hp(550 ... 600 V AC) Three Phase 7.5 Hp
recommended screw driver Pozidriv 2
tightening torque ul/csa Main Circuit 10 ... 12 in·lb
environmental information https://library.abb.com/d/1SAC200049H0009
ex operating instructions https://library.abb.com/d/2CDC131063M6801
general use rating ul/csa (600 V AC) 10 A
minimum mounting distance Electrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
rated operational voltage Main Circuit 690 V ACMain Circuit 250 V DC
object classification code F
contact position indication ON / OFF / TRIP
rated insulation voltage (ui) 690 V
cut-off current characteristic https://library.abb.com/d/1SAM300508F0001, https://library.abb.com/d/1SAM300508F0003
declaration of conformity - ce https://library.abb.com/d/1SAD101100-3402
rated operational current (ie) 10 A
declaration of conformity - ccc https://library.abb.com/d/2020980307003526, https://library.abb.com/d/2020980307003041
connecting capacity main circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm2Flexible 1/2x 0.75 ... 2.5 mm2Rigid 1/2x 1 ... 4 mm2
declaration of conformity - ukca https://library.abb.com/d/1SAD201100-3402
maximum operating voltage ul/csa Main Circuit 600 V AC
data sheet, technical information https://library.abb.com/d/2CDC131021D0202
rated operational power ac-3 (pe) (400 V) Three Phase 4 kW
time-current characteristic curve https://library.abb.com/d/1SAM300505F0110
idea granular category code (igcc) 4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
rated operational power ac-3e (pe) (400 V) Three Phase 4 kW
rated operational current ac-3 (ie) 10 A
rated operational current dc-5 (ie) 10 A
short-circuit current rating (sccr) Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kAManual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kAAny UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
ambient air temperature compensation Yes
rated operational current ac-3e (ie) 10 A
maximum operating altitude permissible 2000 m
rated impulse withstand voltage (uimp) Main Circuit 6 kV
connecting capacity main circuit ul/csa Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
resistance to shock acc. to iec 60068-2-27 11 ms Pulse 25g
conventional free-air thermal current (ith) Main Circuit 10 A
resistance to vibrations acc. to iec 60068-2-6 5g / 3 ... 150 Hz
rated service short-circuit breaking capacity (ics) (230 V AC) 100 kA(250 V DC) 3 Poles in Series 10 kA(400 V AC) 100 kA(440 V AC) 30 kA(500 V AC) 20 kA(690 V AC) 3 kA
rated ultimate short-circuit breaking capacity (icu) (230 V AC) 100 kA(400 V AC) 100 kA(440 V AC) 30 kA(500 V AC) 20 kA(690 V AC) 3 kA
rated instantaneous short-circuit current setting (ii) 150 A