ABB

1SBH101001R2622

Product type: NS22E-26

NS22E-26 Hilfsschütz 230V 50/60Hz, 2S+2Ö

Description

Hilfsschütze NS/NSL erfüllen Relaisfunktion und stehen für die sehr kompakte Baureihe mit AC- oder DC-Ansteuerung. Die 4- oder 8-poligen Geräte schalten Steuerkreise oder Lastkreise bis 4 A (230 V). Anbaubare Zubehörteile sind seitlich einsteckbare Löschglieder, 1-polige, frontseitig aufsteckbare Hilfsschalter.
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.22 KG / psc.
Commodity number85365080
Country of originCN
Dimensions (WxHxD)0.045x0.068x0.073 m
EAN code3471523000261
Product groupSB
eclass V11.1 : 27371001
etim 4 EC000196 - Contactor relay
etim 5 EC000196 - Contactor relay
etim 6 EC000196 - Contactor relay
etim 7 EC000196 - Contactor relay
etim 8 EC000196 - Contactor relay
unspsc 39121529
standards IEC 60947-5-1 and EN 60947-5-1, UL 508, CSA C22.2 N°14
rohs status Following EU Directive 2002/95/EC August 18, 2005 and amendment
operate time Between Coil De-energization and NC Contact Closing 7 ... 22 msBetween Coil De-energization and NO Contact Opening 5 ... 19 msBetween Coil Energization and NC Contact Opening 6 ... 18 msBetween Coil Energization and NO Contact Closing 9 ... 24 ms
terminal type Screw Terminals
cb certificate https://library.abb.com/d/CB_CN_32453
ul certificate https://library.abb.com/d/UL_220108-E312527A
ccc certificate https://library.abb.com/d/CCC_2007010305248106
cqc certificate https://library.abb.com/d/CQC2007010305248106
ul listing card https://library.abb.com/d/NOA_E312527.pdf
gost certificate https://library.abb.com/d/GOST_POCCCNME77B07821.pdf
rohs information https://library.abb.com/d/1SBD251002E1000
climatic withstand Category B according to IEC 60947-1 Annex Q
rated frequency (f) Auxiliary Circuit 50 / 60 Hz
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
wire stripping length Auxiliary Circuit 9 mmControl Circuit 9 mm
ambient air temperature Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... 70 °C
tightening torque ul/csa Auxiliary Circuit 9 in·lbControl Circuit 9 in·lb
environmental information https://library.abb.com/d/1SBD250158E1000
rated operational voltage Auxiliary Circuit 690 VMain Circuit 690 V
object classification code K
rated insulation voltage (ui) acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V
declaration of conformity - ce https://library.abb.com/d/1SBD250016U1000
declaration of conformity - ccc https://library.abb.com/d/2020980304001219
number of auxiliary contacts nc 2
number of auxiliary contacts no 2
declaration of conformity - ukca https://library.abb.com/d/1SBD250051U1000
idea granular category code (igcc) 4755 >> Contactors
rated control circuit voltage (uc) 50 Hz 230 V60 Hz 230 V
connecting capacity control circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Rigid 1/2x 0.75 ... 2.5 mm2
rated operational current ac-15 (ie) (500 V) NC 2(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
rated operational current dc-13 (ie) (24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W
connecting capacity auxiliary circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Rigid 1/2x 0.75 ... 2.5 mm2
maximum electrical switching frequency (AC-15) 1200 cycles per hour(DC-13) 900 cycles per hour
maximum mechanical switching frequency 3600 cycles per hour
maximum operating altitude permissible 3000 m
rated impulse withstand voltage (uimp) Auxiliary Circuit 6 kV
resistance to shock acc. to iec 60068-2-27 Closed, Shock Direction: C1 19 gClosed, Shock Direction: C2 16 gOpen, Shock Direction: C1 8 gOpen, Shock Direction: C2 13 gShock Direction: A 20 gShock Direction: B1 5 gShock Direction: B2 15 g
conventional free-air thermal current (ith) acc. to IEC 60947-5-1, q = 40 °C 10 A
resistance to vibrations acc. to iec 60068-2-6 5 ... 300 Hz 3 g Closed position / 2 g Open position
rated short-time withstand current low voltage (icw) for 0.1 s 140 Afor 1 s 100 A