| Weight | 0.28 KG / psc. |
| Commodity number | 85365080 |
| Country of origin | CN |
| Dimensions (WxHxD) | 0.045x0.068x0.073 m |
| EAN code | 3471523057012 |
| Product group | SB |
| eclass | V11.1 : 27371001 |
| etim 4 | EC000196 - Contactor relay |
| etim 5 | EC000196 - Contactor relay |
| etim 6 | EC000196 - Contactor relay |
| etim 7 | EC000196 - Contactor relay |
| etim 8 | EC000196 - Contactor relay |
| unspsc | 39121529 |
| standards | IEC 60947-5-1 and EN 60947-5-1, UL 508, CSA C22.2 N°14 |
| rohs status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| operate time | Between Coil De-energization and NC Contact Closing 15 ... 20 msBetween Coil De-energization and NO Contact Opening 13 ... 17 msBetween Coil Energization and NC Contact Opening 31 ... 53 msBetween Coil Energization and NO Contact Closing 36 ... 59 ms |
| terminal type | Spring Terminals |
| cb certificate | https://library.abb.com/d/CB_CN_32453 |
| ul certificate | https://library.abb.com/d/UL_220108-E312527A |
| ccc certificate | https://library.abb.com/d/CCC_2007010305248106 |
| cqc certificate | https://library.abb.com/d/CQC2007010305248106 |
| gost certificate | https://library.abb.com/d/GOST_POCCCNME77B07821.pdf |
| rohs information | https://library.abb.com/d/1SBD251008E1000 |
| climatic withstand | Category B according to IEC 60947-1 Annex Q |
| rated frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| degree of protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| wire stripping length | Auxiliary Circuit 10 mmControl Circuit 10 mm |
| ambient air temperature | Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... 70 °C |
| environmental information | https://library.abb.com/d/1SBD250161E1000 |
| rated operational voltage | Auxiliary Circuit 690 VMain Circuit 690 V |
| object classification code | K |
| rated insulation voltage (ui) | acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V |
| declaration of conformity - ce | https://library.abb.com/d/1SBD250016U1000 |
| declaration of conformity - ccc | https://library.abb.com/d/2020980304001219 |
| number of auxiliary contacts nc | 0 |
| number of auxiliary contacts no | 4 |
| declaration of conformity - ukca | https://library.abb.com/d/1SBD250051U1000 |
| idea granular category code (igcc) | 4755 >> Contactors |
| rated control circuit voltage (uc) | DC Operation 24 V |
| connecting capacity control circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm2Rigid 1/2x 0.75 ... 2.5 mm2 |
| rated operational current ac-15 (ie) | (500 V) NC 2(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A |
| rated operational current dc-13 (ie) | (24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W |
| connecting capacity auxiliary circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm2Rigid 1/2x 0.75 ... 2.5 mm2 |
| maximum electrical switching frequency | (AC-15) 1200 cycles per hour(DC-13) 900 cycles per hour |
| maximum mechanical switching frequency | 3600 cycles per hour |
| maximum operating altitude permissible | 3000 m |
| rated impulse withstand voltage (uimp) | Auxiliary Circuit 6 kV |
| resistance to shock acc. to iec 60068-2-27 | Closed, Shock Direction: A 20 gClosed, Shock Direction: B1 15 gClosed, Shock Direction: C1 19 gClosed, Shock Direction: C2 14 gOpen, Shock Direction: A 10 gOpen, Shock Direction: B1 5 gOpen, Shock Direction: C1 8 gOpen, Shock Direction: C2 8 gShock Direction: B2 10 g |
| conventional free-air thermal current (ith) | acc. to IEC 60947-5-1, q = 40 °C 10 A |
| resistance to vibrations acc. to iec 60068-2-6 | 5 ... 300 Hz 3 g Closed position / 2 g Open position |
| rated short-time withstand current low voltage (icw) | for 0.1 s 140 Afor 1 s 100 A |