ABB

1SBL236063R2300

Product type: AF26ZB-30-00K-23

AF26ZB-30-00K-23 100-250V50/60HZ-DC Contactor

RoHS Compliant

Description

The AF26ZB-30-00K-23 is a 3 pole - 690 V IEC or 600 UL contactor with Push-in spring terminals, controlling motors up to 11 kW / 400 V AC (AC-3) or 15 hp / 480 V UL and switching power circuits up to 42 A (AC-1) or 45 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. AF26ZB-30-00K-23
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
  • AF Contactors
  • AF26
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.33 KG / psc.
Commodity number85364900
Country of originFR
Dimensions (WxHxD)93x45x86 mm
EAN code3471523009912
Product groupSR
eclass V11.0 : 27371003
etim 4 EC000066 - Magnet contactor, AC-switching
etim 5 EC000066 - Magnet contactor, AC-switching
etim 6 EC000066 - Power contactor, AC switching
etim 7 EC000066 - Power contactor, AC switching
etim 8 EC000066 - Power contactor, AC switching
unspsc 39121529
nema size 1
standards IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
operate time Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms
terminal type Push-in Spring Terminals
cb certificate https://library.abb.com/d/CB_SE-96552
ccc certificate https://library.abb.com/d/CCC_2010010304445623
cqc certificate https://library.abb.com/d/CQC2010010304445623
cul certificate https://library.abb.com/d/UL_20180227_E312527_7_1
climatic withstand Category B according to IEC 60947-1 Annex Q
rated frequency (f) Main Circuit 50 / 60 Hz
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
wire stripping length Auxiliary Circuit 0 mmControl Circuit 10 mmMain Circuit 14 mm
horsepower rating nema (115 V AC) Single Phase 2 Hp(200 V AC) Three Phase 7-1/2 Hp(230 V AC) Single Phase 3 Hp(230 V AC) Three Phase 7-1/2 Hp(460 V AC) Three Phase 10 Hp(575 V AC) Three Phase 10 Hp
ambient air temperature Close to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
horsepower rating ul/csa (120 V AC) Single Phase 2 hp(200 ... 208 V AC) Three Phase 7-1/2 hp(220 ... 240 V AC) Three Phase 7-1/2 hp(240 V AC) Single Phase 3 hp(440 ... 480 V AC) Three Phase 15 hp(550 ... 600 V AC) Three Phase 20 hp
general use rating ul/csa (600 V AC) 42 A
maximum breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A
rated operational voltage Main Circuit 690 V
number of main contacts nc 0
number of main contacts no 3
object classification code Q
rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 Vacc. to UL/CSA 600 V
continuous current rating nema 27 A
declaration of conformity - ce https://library.abb.com/d/1SBD250002U1000
declaration of conformity - ccc https://library.abb.com/d/2020980304001254
number of auxiliary contacts nc 0
number of auxiliary contacts no 0
connecting capacity main circuit Flexible with Ferrule 1/2x 1 ... 6 mm2Flexible with Insulated Ferrule 1/2x 1 ... 6 mm2Flexible 1/2x 1 ... 6 mm2Rigid 1/2x 1 ... 10 mm2
declaration of conformity - ukca https://library.abb.com/d/1SBD250033U1000
data sheet, technical information https://library.abb.com/d/1SBC100220C0201
mounting by screws (not supplied) 2 x M4 screws placed diagonally
rated operational power ac-3 (pe) (415 V) 11 kW(440 V) 15 kW(500 V) 15 kW(690 V) 15 kW(380 / 400 V) 11 kW(220 / 230 / 240 V) 6.5 kW
rated control circuit voltage (uc) 50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
rated operational power ac-3e (pe) (415 V) 11 kW(440 V) 15 kW(500 V) 15 kW(690 V) 15 kW(380 / 400 V) 11 kW(220 / 230 / 240 V) 6.5 kW
connecting capacity control circuit Flexible with Ferrule 1/2x 0.5 ... 2.5 mm2Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm2Flexible 1/2x 0.5 ... 2.5 mm2Rigid 1/2x 1 ... 2.5 mm2
rated operational current ac-1 (ie) (690 V) 40 °C 45 A(690 V) 60 °C 40 A(690 V) 70 °C 32 A
rated operational current ac-3 (ie) (415 V) 60 °C 26 A(440 V) 60 °C 26 A(500 V) 60 °C 23 A(690 V) 60 °C 17 A(380 / 400 V) 60 °C 26 A(220 / 230 / 240 V) 60 °C 26 A
rated operational current ac-3e (ie) (415 V) 60 °C 26 A(440 V) 60 °C 26 A(500 V) 60 °C 23 A(690 V) 60 °C 17 A(380 / 400 V) 60 °C 26 A(220 / 230 / 240 V) 60 °C 26 A
maximum electrical switching frequency (AC-1) 600 cycles per hour(AC-15) 0 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour(DC-13) 0 cycles per hour
maximum mechanical switching frequency 3600 cycles per hour
maximum operating altitude permissible Without Derating 3000 m
rated impulse withstand voltage (uimp) 6 kV
conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 50 A
resistance to vibrations acc. to iec 60068-2-6 5 ... 300 Hz 4 g closed position / 2 g open position
rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A