Product type: UA30-30-10RA 220-230V 50Hz / 230-240V 60
UA30-30-10RA 220-230V 50Hz / 230-240V 60Hz Contactor
Description
| Thomas Hoffmann |
| +49 305 201 4443 |
| sales@zwodltd.com |
| Price: Please send request |
| Request Lead Time: app. 1 Day |
| Delivery Time: app. 6-9 Weeks Estimated delivery time to our warehouse in Berlin |
| Delivery Terms: FCA Berlin individually for each client according to INCOM TERMS 2025 |
| Product Attribute | Attribute Value |
|---|---|
| Weight | 0.81 KG / psc. |
| Commodity number | 85364900 |
| Country of origin | FR |
| Dimensions (WxHxD) | 54x130x141 mm |
| EAN code | 3471522302809 |
| Product group | SB |
| eclass | V11.0 : 27371006 |
| etim 4 | EC001079 - Capacitor magnet contactor |
| etim 5 | EC001079 - Capacitor magnet contactor |
| etim 6 | EC001079 - Capacitor contactor |
| etim 7 | EC001079 - Capacitor contactor |
| etim 8 | EC001079 - Capacitor contactor |
| unspsc | 39121529 |
| rohs status | Following EU Directive 2011/65/EU |
| operate time | Between Coil De-energization and NO Contact Opening 4 ... 11 msBetween Coil Energization and NO Contact Closing 8 ... 21 ms |
| terminal type | Screw Terminals |
| cb certificate | https://library.abb.com/d/CB_FR3448_60016915-509739C |
| ccc certificate | https://library.abb.com/d/CCC_2004010304138316 |
| cqc certificate | https://library.abb.com/d/CQC2003010304060095, https://library.abb.com/d/CQC2007010309256050 |
| csa certificate | https://library.abb.com/d/CSA_1033838_LR056745 |
| coil consumption | Average Holding Value 50 / 60 Hz 12 V·AAverage Holding Value 50 Hz 12 V·AAverage Holding Value 60 Hz 12 V·AAverage Pull-in Value 50 Hz 120 V·AAverage Pull-in Value 60 Hz 140 V·A |
| gost certificate | https://library.abb.com/d/GOST_POCCFRME77B07175 |
| rohs information | https://library.abb.com/d/1SBD250805U1000 |
| dimension diagram | https://library.abb.com/d/FPTE307845 |
| climatic withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| e-number (finland) | 3709165 |
| rated frequency (f) | Supply Circuit 50 / 60 Hz |
| degree of protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
| mounting on din rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| ambient air temperature | Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... 55 °CNear Contactor for Operation in Free Air (Uc) -40 ... 70 °C |
| environmental information | https://library.abb.com/d/1SBD250123E1000 |
| maximum breaking capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A |
| rated operational voltage | Auxiliary Circuit 690 VMain Circuit 690 V |
| number of main contacts nc | 0 |
| number of main contacts no | 3 |
| object classification code | Q |
| rated insulation voltage (ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V |
| declaration of conformity - ce | https://library.abb.com/d/1SBD250805U1000 |
| declaration of conformity - ccc | https://library.abb.com/d/2020980304001610, https://library.abb.com/d/2020980304001216 |
| number of auxiliary contacts nc | 0 |
| number of auxiliary contacts no | 1 |
| connecting capacity main circuit | Flexible with Cable End 2.5 ... 4 mm2Rigid Cable 2.5 ... 6 mm2 |
| declaration of conformity - ukca | https://library.abb.com/d/1SBD250822U1000 |
| short-circuit protective devices | Auxiliary Circuit - gG Type Fuses 10 AgG Type Fuses 200 A |
| data sheet, technical information | https://library.abb.com/d/1SBC101140C0203 |
| mounting by screws (not supplied) | 2 x M4 screws placed diagonally |
| rated control circuit voltage (uc) | 50 Hz 220 ... 230 V60 Hz 230 ... 240 V |
| rated operational power ac-6b (pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 16 kvar(230 / 240 V) 55 °C, 50 / 60 Hz 16 kvar(230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar(400 / 415 V) 40 °C, 50 / 60 Hz 30 kvar(400 / 415 V) 70 °C, 50 / 60 Hz 19.5 kvar(400 / 415 V) 55 °C, 50 / 60 Hz 27.5 kvar(440 V) 40 °C, 50 / 60 Hz 32 kvar(440 V) 55 °C, 50 / 60 Hz 30 kvar(440 V) 70 °C, 50 / 60 Hz 20.5 kvar(500 / 550 V), 40 °C, 50 / 60 Hz 34 kvar(500 / 550 V) 55 °C, 50 / 60 Hz 34 kvar(500 / 550 V) 70 °C, 50 / 60 Hz 25 kvar(690 V) 40 °C, 50 / 60 Hz 45 kvar(690 V) 55 °C, 50 / 60 Hz 45 kvar(690 V) 70 °C, 50 / 60 Hz 32 kvar |
| rated operational current ac-15 (ie) | (500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(380 / 400 V) 3 A |
| rated operational current dc-13 (ie) | (24 V) 6 / 144 A(48 V) 2.8 / 134 A(72 V) 2 / 144 A(125 V) 1.1 / 138 A(250 V) 0.55 / 138 A |
| connecting capacity auxiliary circuit | Flexible with Cable End 0.75 ... 2.5 mm2Rigid Cable 1 ... 4 mm2 |
| maximum electrical switching frequency | 240 cycles per hour |
| maximum operating altitude permissible | Without Derating 3000 m |
| rated impulse withstand voltage (uimp) | 8 kV |
| conventional free-air thermal current (ith) | acc. to IEC 60947-5-1, q = 40 °C 16 A |
| connecting terminals (delivered in open position) main poles | M 5 (+,-) pozidriv 2 screws with 2x (5.6x6.5 mm) connector |