ABB

1SBL407082R1122

Product type: AFS96-30-22-11

AFS96-30-22-11 24-60V50/60HZ 20-60VDC Contactor

Description

The AFS96-30-22-11 is a 3 pole - 1000 V IEC or 600 V UL contactor with fixed 2 N.O + 2 N.C. front mounted auxiliary contact blocks with screw connections, controlling motors up to 45 kW / 400 V AC (AC-3) or 60 hp / 480 V UL and switching power circuits up to 130 A (AC-1) or 115 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (24 ... 60 V), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. AFS96-30-22-11
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
  • AFS Contactors
  • AFS96
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight1.27 KG / psc.
Commodity number85364900
Country of originFR
Dimensions (WxHxD)167x97x180 mm
EAN code3471523158016
Product groupSB
eclass V11.0 : 27371003
etim 4 EC000066 - Magnet contactor, AC-switching
etim 5 EC000066 - Magnet contactor, AC-switching
etim 6 EC000066 - Power contactor, AC switching
etim 7 EC000066 - Power contactor, AC switching
etim 8 EC000066 - Power contactor, AC switching
rohs status Following EU Directive 2011/65/EU
operate time Between Coil De-energization and NC Contact Closing 19 ... 105 msBetween Coil De-energization and NO Contact Opening 17 ... 100 msBetween Coil Energization and NC Contact Opening 38 ... 95 msBetween Coil Energization and NO Contact Closing 42 ... 100 ms
terminal type Screw Terminals
bv certificate https://library.abb.com/d/BV_2634H36994A
cb certificate https://library.abb.com/d/CB_SE-96557
gl certificate https://library.abb.com/d/DNV-GL_TAE00001AF-3
abs certificate https://library.abb.com/d/ABS_20-2060694-PDA
ccc certificate https://library.abb.com/d/CCC_2013010304646569
cqc certificate https://library.abb.com/d/CQC2013010304646569
cul certificate https://library.abb.com/d/UL_20170607-E312527-14-1
eac certificate https://library.abb.com/d/EAC_RUC-FRME77B03199
ul listing card https://library.abb.com/d/E312527
rmrs certificate https://library.abb.com/d/RMRS_1802705280
rohs information https://library.abb.com/d/1SBD250022U1000
dimension diagram https://library.abb.com/d/DNV_TAE00001AF-4
e-number (sweden) 3210675
climatic withstand Category B according to IEC 60947-1 Annex Q
e-number (finland) 3708061
rated frequency (f) Auxiliary Circuit 50 / 60 HzMain Circuit 50 / 60 Hz
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
wire stripping length Auxiliary Circuit 10 mmControl Circuit 10 mmMain Circuit 17 mm
ambient air temperature Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °CClose to Contactor without Thermal O/L Relay -40 ... 70 °CClose to Contactor for Storage -60 ... +80 °C
horsepower rating ul/csa (120 V AC) Single Phase 7-1/2 hp(200 ... 208 V AC) Three Phase 30 hp(220 ... 240 V AC) Three Phase 40 hp(240 V AC) Single Phase 20 hp(440 ... 480 V AC) Three Phase 75 hp(550 ... 600 V AC) Three Phase 75 hp
tightening torque ul/csa Auxiliary Circuit 11 in·lbControl Circuit 11 in·lbMain Circuit 53 in·lb
general use rating ul/csa (600 V AC) 115 A
maximum breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A
rated operational voltage Auxiliary Circuit 690 VMain Circuit 1000 V
number of main contacts nc 0
number of main contacts no 3
object classification code Q
rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
declaration of conformity - ce https://library.abb.com/d/1SBD250022U1000
declaration of conformity - ccc https://library.abb.com/d/2020980304001255
number of auxiliary contacts nc 2
number of auxiliary contacts no 2
connecting capacity main circuit Flexible with Ferrule 1/2x 6 ... 50 mm2Flexible with Insulated Ferrule 1/2x 6 ... 50 mm2Rigid 1x 6 ... 70 mm2Rigid 2x 6 ... 50 mm2
declaration of conformity - ukca https://library.abb.com/d/1SBD250044U1000
mounting by screws (not supplied) 2 x M4 or 2 x M6 screws placed diagonally
rated operational power ac-3 (pe) (415 V) 55 kW(440 V) 55 kW(500 V) 55 kW(690 V) 55 kW(1000 V) 40 kW(380 / 400 V) 45 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 25 kW(220 / 230 / 240 V) 30 kW
rated control circuit voltage (uc) 50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V
rated operational power ac-3e (pe) (415 V) 55 kW(440 V) 55 kW(500 V) 55 kW(690 V) 55 kW(380 / 400 V) 45 kW(380 / 400 V) 55 kW(220 / 230 / 240 V) 25 kW(220 / 230 / 240 V) 30 kW
connecting capacity control circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Rigid 1/2x 1 ... 2.5 mm2
rated operational current ac-1 (ie) (690 V) 40 °C 130 A(690 V) 60 °C 105 A(690 V) 70 °C 90 A
rated operational current ac-3 (ie) (415 V) 60 °C 96 A(440 V) 60 °C 96 A(500 V) 60 °C 80 A(690 V) 60 °C 57 A(1000 V) 60 °C 30 A(380 / 400 V) 60 °C 105 A(220 / 230 / 240 V) 60 °C 105 A
rated operational current ac-15 (ie) (500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A
rated operational current ac-3e (ie) (415 V) 60 °C 96 A(440 V) 60 °C 96 A(500 V) 60 °C 80 A(690 V) 60 °C 57 A(380 / 400 V) 60 °C 105 A(220 / 230 / 240 V) 60 °C 105 A
rated operational current dc-13 (ie) (24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W
connecting capacity auxiliary circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm2Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm2Rigid 1/2x 1 ... 2.5 mm2
maximum electrical switching frequency (AC-1) 600 cycles per hour(AC-15) 1200 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 1200 cycles per hour(DC-13) 900 cycles per hour
maximum mechanical switching frequency 3600 cycles per hour
maximum operating altitude permissible Without Derating 3000 m
rated impulse withstand voltage (uimp) 8 kV
resistance to shock acc. to iec 60068-2-27 Closed, Shock Direction: A 25 gClosed, Shock Direction: B1 25 gClosed, Shock Direction: B2 15 gClosed, Shock Direction: C1 25 gClosed, Shock Direction: C2 25 g
conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 130 Aacc. to IEC 60947-5-1, q = 40 °C 16 A
resistance to vibrations acc. to iec 60068-2-6 5 ... 300 Hz 3 g closed position / 3 g open position
rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 Afor 0.1 s 140 Afor 1 s 100 A