ABB

1SCA115286R1001

Product type: OTM160E3WM230C

OTM160E3WM230C MOTORIZED SWITCH

RoHS Compliant

Description

3-pole, motor operated, base mounted switch-diconnector with handle for manual operation, terminal bolt kit, handle and spare fuse storage clip and male connector for control circuit, wide phase distance OTM160E3WM230C
  • Low Voltage Products and Systems
  • Switches
  • Motorized Switch-Disconnectors
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight5.2 KG / psc.
Commodity number85365080
Country of originFI
Dimensions (WxHxD)215x215x395 mm
EAN code6417019476742
Product groupFA
eclass V11.1 : 27371403
etim 5 EC000216 - Switch disconnector
etim 6 EC000216 - Switch disconnector
etim 7 EC000216 - Switch disconnector
etim 8 EC000216 - Switch disconnector
lock type Yes
standards IEC 60947-3
power loss at Rated Operating Conditions per Pole 3.2 W
handle type Direct mounted handle
rohs status Following EU Directive 2011/65/EU
handle color Black
mounting type Base mounting
terminal type Screw Terminals
weee category 5. Small Equipment (No External Dimension More Than 50 cm)
operating mode Front operated
number of poles 3
pollution degree 3
rohs information https://library.abb.com/d/1SCC301197D2703
special functions Wide phase distance
tightening torque acc. IEC 60947-1 15 ... 22 N·m
degree of protection Front IP00
mechanical durability 20000
distance between phases Wide phase distance
motor operational voltage 220 ... 240 V AC
rated operational voltage Main Circuit 1000 V
object classification code Q
position of line terminals Top In - Bottom Out
switches operating mechanism Mechanism at the End of the Switch
rated insulation voltage (ui) acc. to IEC/EN 60664-1 1000 V
declaration of conformity - ce https://library.abb.com/d/1SCC301197D0202
data sheet, technical information https://library.abb.com/d/1SCC301020C0201
conventional thermal current (ithe) Fully Enclosed 160 A
rated operational power ac-23a (pe) (220 ... 240 V) 48 kW(400 ... 415 V) 80 kW(500 V) 112 kW(690 V) 144 kW
rated operational current ac-21a (ie) (380 ... 415 V) 200 A(500 V) 200 A(690 V) 160 A(1000 V AC) 160 A
rated operational current ac-22a (ie) (380 ... 415 V) 200 A(500 V) 200 A(690 V) 160 A
rated operational current ac-23a (ie) (380 ... 415 V) 160 A(500 V) 160 A(690 V) 160 A
rated impulse withstand voltage (uimp) 12 kV
rated short-circuit making capacity (icm) (690 V) 30 kA
conventional free-air thermal current (ith) q = 40 °C 200 A
rated conditional short-circuit current (inc) (315 A fuse, 500 V) 100 kA(355 A fuse, 690 V) 80 kA
rated short-time withstand current low voltage (icw) for 1 s 8 kA