ABB

1SCA118850R1001

Product type: OSM1250D4N2M230C

OSM1250D4N2M230C MOTORIZED SWITCH FUSE

RoHS Compliant

Description

Motorized switch-disconnector fuse, 1250A, 4-pole, DIN 4, switched non-fusible fourth pole, motor voltage Ue = 220-240 VAC, including a handle for manual operation and male connectors for control circuit and a handle and spare fuse storage clip. OSM1250D4N2M230C
  • Low Voltage Products and Systems
  • Switches
  • Motorized Switch Fuses
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight63.5 KG / psc.
Commodity number85365080
Country of originFI
Dimensions (WxHxD)590x500x790 mm
EAN code6417019505176
Product groupFA
etim 5 EC001040 - Fuse switch disconnector
etim 6 EC001040 - Fuse switch disconnector
fuse size NH4
standards IEC 60947-3
power loss at Rated Operating Conditions per Pole 75 W
fuse system DIN
handle type Handle included for manual operation
mounting type Base mounting
terminal type Lug terminals
weee category 4. Large Equipment (Any External Dimension More Than 50 cm)
operating mode Motor operated and manually from the front
number of poles 4
fourth pole type Switched - With Solid Link
pollution degree 3
rated current (in) Main Circuit 1250 A
fourth pole position Right Side
environmental information https://library.abb.com/d/1SCC311002D0201
motor operational voltage 220 ... 240 V AC
rated operational voltage Main Circuit 690 V AC
object classification code Q
position of line terminals Top In - Bottom Out, Bottom In - Top Out
switches operating mechanism 04 (Left Side)
rated insulation voltage (ui) 1000 V
declaration of conformity - ce https://library.abb.com/d/No declaration needed
data sheet, technical information https://library.abb.com/d/1SCC311013C0201
rated operational power ac-23a (pe) (380 ... 415 V) 560 kW(500 V) 710 kW(690 V) 1000 kW
rated operational current ac-21a (ie) (380 ... 415 V) 1250 A(500 V AC) 1250 A(690 V AC) 1250 A
rated operational current ac-22a (ie) (380 ... 415 V) 1250 A(500 V) 1250 A(690 V) 1250 A
rated operational current ac-23a (ie) (380 ... 415 V) 1000 A(500 V) 1000 A(690 V) 1000 A
rated impulse withstand voltage (uimp) 12 kV
conventional free-air thermal current (ith) q = 40 °C 1250 A
rated conditional short-circuit current (inc) (690 V) 80 kA
rated short-time withstand current low voltage (icw) for 1 s 40 kiloampere rms