ABB

1SCA158854R1001

Product type: OTDC800F11K

OTDC800F11K DC Switch-disconnector

Description

A fully optimized two-pole DC switch-disconnector for 1000V utility-scale photovoltaic power plants covering 315-800A current range. The new design offers both a size reduction and an increase in efficiency and performance.The two-pole 1000V DC Switch helps manufacturers improve system efficiency. Measuring just 150mm wide and 122mm high, the compact size of the new OTDC range makes it possible for manufacturers to reduce the size of combiner boxes and inverters.Main characteristics for this particular OTDC type:Disconnect single PV circuit, Approved according to IEC 60947-1, -3
  • Low Voltage Products and Systems
  • Switches
  • DC Switch-Disconnectors
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 4-5 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight3.8 KG / psc.
Commodity number85363090
Country of originFI
Dimensions (WxHxD)177.5x211x169.5 mm
EAN code6417019882109
Product groupFA
eclass V11.1 : 27371403
etim 5 EC000216 - Switch disconnector
etim 6 EC000216 - Switch disconnector
etim 7 EC000216 - Switch disconnector
etim 8 EC000216 - Switch disconnector
standards IEC 60947-1, -3
power loss at Rated Operating Conditions per Pole 30...32 W
handle type Direct mounted handle
rohs status Following EU Directive 2011/65/EU
utilization Photovoltaic
handle color Black
shaft length 160 mm6.3 in
handle length 95 mm3.7 in
mounting type Base mounting
terminal type Lug terminals
weee category 5. Small Equipment (No External Dimension More Than 50 cm)
operating mode Front Operated
shaft diameter 12 mm0.47 in
terminal width 30 mm1.2 in
wiring diagram https://library.abb.com/d/1SCC301030K0201
ccc certificate https://library.abb.com/d/CQC2019010302206498
number of poles 2
pollution degree 3
rohs information https://library.abb.com/d/1SCC301227D2701
special functions No
tightening torque Cable Lug 30 ... 40 N·m
dnv gl certificate https://library.abb.com/d/1SCC301231D0201
last ordering date 2022-11-30 All Countries
number of circuits 1
product frame size M
mechanical drawings https://library.abb.com/d/OTDC315-630FV11K_stp, https://library.abb.com/d/OTDC315-630FV11K_igs
degree of protection Front IP20
utilization category Switching of resistive loads, including moderate overloads - occasional actuation (DC-21B)Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) - occasional actuation (DC-22B)Switching of single PV string(s) without reverse and overcurrents (DC-PV1)Switching of several PV string(s) with reverse and overcurrents (DC-PV2)
mechanical durability 10000 cycle
connection configuration Single circuit 2a, 2b
rated operational voltage 1000 V
object classification code Q
position of line terminals Top In - Bottom OutBottom In - Top Out
switches operating mechanism Mechanism Between the Poles11 (Between the Poles)
rated insulation voltage (ui) 1500 V
declaration of conformity - ce https://library.abb.com/d/1SCC301227D2701
rated operational current dc-22b (1000 V) 400 A
rated operational current dc-pv1 (1000 V) 500 A
rated operational current dc-pv2 (1000 V) 500 A
data sheet, technical information https://library.abb.com/d/1SCC301022C0201
conventional thermal current (ithe) Fully Enclosed 630 A
rated operational current dc-21b (ie) (1000 V) 800 A
rated impulse withstand voltage (uimp) 12 kV
rated short-circuit making capacity (icm) (1000 V DC) 10 kA
conventional free-air thermal current (ith) q = 40 °C 800 A
rated short-time withstand current low voltage (icw) (1500 V DC) 10 kAfor 1 s 10 kA
positive opening operation torque (direct opening action) 11 ... 19 N·m