| Weight | 10 KG / psc. |
| Commodity number | 85364900 |
| Country of origin | SE |
| Dimensions (WxHxD) | 555x500x365 mm |
| EAN code | 7320500513880 |
| Product group | SE |
| eclass | V11.1 : 27371502 |
| etim 4 | EC001080 - Electronic overload relay |
| etim 5 | EC001080 - Electronic overload relay |
| etim 6 | EC001080 - Electronic overload relay |
| etim 7 | EC001080 - Electronic overload relay |
| etim 8 | EC001080 - Electronic overload relay |
| unspsc | 39121500 |
| standards | IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-4-1 |
| rohs status | Following EU Directive 2011/65/EU |
| suitable for | AF1350AF1650AF2050 |
| setting range | 375 ... 1250 A |
| number of poles | 3 |
| pollution degree | 3 |
| rohs information | https://library.abb.com/d/2CMT2016-005489 |
| mounting position | 1 ... 6 |
| tightening torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| rated frequency (f) | Main Circuit 60 Hz |
| ampere rating ul/csa | 1250 A |
| degree of protection | Auxiliary Circuit Terminals IP20Main Circuit Terminals IP00 |
| contact rating ul/csa | (NC:) B600(NC:) Q300(NO:) B600(NO:) Q300 |
| wire stripping length | 9 mm |
| ambient air temperature | Operation -25 ... +70 °COperation Compensated -25 ... +70 °CStorage -50 ... +80 °C |
| recommended screw driver | Auxiliary Circuit Pozidriv 2 |
| tightening torque ul/csa | Auxiliary Circuit 7 ... 11 in·lb |
| rated operational voltage | Auxiliary Circuit 600 VMain Circuit 1000 V |
| rated insulation voltage (ui) | AC 1000 VInput Circuit / Output Circuit 690 V |
| declaration of conformity - ce | https://library.abb.com/d/2CMT2015-005441 |
| rated operational current (ie) | 1250 A |
| number of auxiliary contacts nc | 1 |
| number of auxiliary contacts no | 1 |
| connecting capacity main circuit | Busbar 80x10 mm2 |
| declaration of conformity - ukca | https://library.abb.com/d/2CMT2020-006120 |
| maximum operating voltage ul/csa | Main Circuit 600 V |
| data sheet, technical information | https://library.abb.com/d/1SBC100214C0201 |
| rated operational current ac-3 (ie) | 1250 |
| ambient air temperature compensation | Yes |
| rated operational current ac-15 (ie) | (120 V) NC 3(120 V) NO 3 A(240 V) NC 3 A(400 V) NC 1.1(400 V) NO 1.1 A(500 V) NC 0.75(500 V) NO 0.75 A |
| rated operational current dc-13 (ie) | (125 V) NC 0.55 A(125 V) NO 0.55(24 V) NC 1.5(24 V) NO 1.5(250 V) NC 0.27(250 V) NO 0.27(60 V) NC 0.55(60 V) NO 0.55 |
| connecting capacity auxiliary circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm2Flexible 1/2x 0.75 ... 2.5 mm2Rigid 1/2x 1 ... 4 mm2 |
| maximum operating altitude permissible | Without Derating 2000 m |
| rated impulse withstand voltage (uimp) | Auxiliary Circuit 6 kVMain Circuit 8 kV |
| connecting capacity main circuit ul/csa | Busbar 3.15x0.39 in |
| resistance to shock acc. to iec 60068-2-27 | 11 ms Pulse 15g |
| conventional free-air thermal current (ith) | Auxiliary Circuit NC 6 AAuxiliary Circuit NO 6 A |
| connecting capacity auxiliary circuit ul/csa | Flexible 1/2x 18-10 AWGStranded 1/2x 18-10 AWG |
| resistance to vibrations acc. to iec 60068-2-6 | 3g / 3 ... 150Hz |