| Weight | 63.3 KG / psc. |
| Commodity number | 85371091 |
| Country of origin | SE |
| Dimensions (WxHxD) | 600x800x616 mm |
| EAN code | 7320500510483 |
| Product group | SG |
| eclass | V11.0 : 27370907 |
| etim 4 | EC002572 - Electronic motor control and protection device |
| etim 5 | EC002572 - Electronic motor control and protection device |
| etim 6 | EC002572 - Motor management device |
| unspsc | 39121521 |
| ramp time | 1 ... 120 second [unit of time] |
| rohs status | Following EU Directive 2002/95/EC August 18, 2005 and amendment |
| communication | Built in Modbus interface, Anybus, FieldBusPlug (with adapter). |
| terminal type | Main Circuit: Bars |
| analog outputs | 0...10 V, 0...20 mA, 4...20 mA |
| cqc certificate | https://library.abb.com/d/CN: CQC2015010304830298 / SE: CQC2015010304830294 |
| rohs information | https://library.abb.com/d/2CMT005210 |
| run signal relay | Yes |
| product main type | PSTX1250 |
| tightening torque | Main Circuit 45 N·m |
| fault signal relay | Yes |
| overload protection | Built-in electronic overload protection |
| rated frequency (f) | 50/60 HzMain Circuit 50 / 60 Hz |
| abb type designation | PSTX1250-690-70 |
| ampere rating ul/csa | 1250 A |
| by-pass signal relay | Yes |
| degree of protection | IP00 |
| overload signal relay | Yes |
| current limit function | 1.5 ... 7.5 xle |
| ambient air temperature | Operation -25 ... +60 °CStorage -40 ... +70 °C |
| global commercial alias | PSTX1250-690-70 |
| tightening torque ul/csa | Main Circuit 398.3 |
| environmental information | https://library.abb.com/d/2CMT005232 |
| rated operational voltage | 208 ... 690 V AC |
| service factor percentage | 100 % |
| object classification code | Q |
| initial voltage during start | 10 ... 99 A |
| signal indication fault (led) | Red |
| declaration of conformity - ce | https://library.abb.com/d/2CMT005209 |
| integrated electronic overload | Yes |
| step down voltage special ramp | 100 ... 10 % |
| declaration of conformity - ccc | https://library.abb.com/d/CN: 2020980304001097 / SE: 2020980304001508 |
| maximum operating voltage ul/csa | Main Circuit 690 V |
| adjustable rated motor current ie | 30 ... 100 % |
| data sheet, technical information | https://library.abb.com/d/1SFC132012C0201 |
| rated control supply voltage (us) | 100 ... 250 V AC |
| signal indication running r (led) | Green |
| connecting capacity supply circuit | Rigid 1 x 2.5 mm2 |
| rated control circuit voltage (uc) | DC Operation 24 V |
| signal indication protection (led) | Yellow |
| switch for inside delta connection | Yes |
| connecting capacity control circuit | Rigid 1 x 2.5 mm2 |
| starting capacity at maximum rated current ie | 4xIe for 10s |
| rated operational power - in-line connection (pe) | (230 V) 400 kW(400 V) 710 kW(500 V) 880 kW(690 V) 1200 kW |
| rated operational power - inside delta connection | at 230 V 670 kWat 400 V 1200 kWat 500 V 1500 kWat 690 V 2000 kW |
| signal indication ready to start/standby on (led) | Green |
| rated operational current - in-line connection (ie) | 1250 A |
| rated operational current - inside delta connection | 2160 A |