GAF300-10-11 20-60V DC Contactor

Description

A 3-pole Contactor suitable for DC-1 applications where all three poles must be connected in series in a 1-pole configuration up to max 1000 VDC. Operated with wide control voltage range 20-60 V, DC
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight5.5 KG / psc.
Commodity number85364900
Country of originSE
Dimensions (WxHxD)140x227x180.5 mm
EAN code7320500400876
Product groupSC
eclass V11.0 : 27371018
etim 4 EC002552 - Power contactor, DC switching
etim 5 EC002552 - Power contactor, DC switching
etim 6 EC002552 - Power contactor, DC switching
etim 7 EC002552 - Power contactor, DC switching
etim 8 EC002552 - Power contactor, DC switching
unspsc 39121529
rohs status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
terminal type Main Circuit: Bars
cb certificate https://library.abb.com/d/SEMKO_SE-70017
cqc certificate https://library.abb.com/d/CQC2013010304595899
eac certificate https://library.abb.com/d/9AKK107046A8618
ul listing card https://library.abb.com/d/UL_E73397
coil consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage DC 520 V·A
rohs information https://library.abb.com/d/2CMT003517
dimension diagram https://library.abb.com/d/53540930-2
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
coil operating limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
mechanical durability 5 million
ambient air temperature Operation -40 ... +80 °CStorage -40 ... +70 °C
environmental information https://library.abb.com/d/1SFC101066D0201
general use rating ul/csa (1000 V DC) 400 A(440 V DC) 400 A(600 V DC) 400 A
maximum breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
rated operational voltage Main Circuit 1000 V
number of main contacts nc 0
number of main contacts no 1
object classification code Q
rated insulation voltage (ui) acc. to UL/CSA 1000 V
declaration of conformity - ce https://library.abb.com/d/2CMT003517
declaration of conformity - ccc https://library.abb.com/d/2020980304001540
number of auxiliary contacts nc 1
number of auxiliary contacts no 1
connecting capacity main circuit Bar 32 mm2Rigid Al-Cable 2 x 95 ... 120 mm2Rigid Cu-Cable 16 ... 240 mm2
declaration of conformity - ukca https://library.abb.com/d/2CMT2020-006118
maximum operating voltage ul/csa Main Circuit 600 V
data sheet, technical information https://library.abb.com/d/1SBC100192C0206
idea granular category code (igcc) 4763 >> Power contactor, DC switching
rated control circuit voltage (uc) DC Operation 20 ... 60 V
rated operational current dc-1 (ie) (1000 V) 3 Poles in Series, 40 °C 500 A(1000 V) 3 Poles in Series, 55 °C 400 A(1000 V) 3 Poles in Series, 70 °C 325 A(220 V) 3 Poles in Series, 40 °C 500 A(220 V) 3 Poles in Series, 55 °C 400 A(220 V) 3 Poles in Series, 70 °C 325 A(400 V) 3 Poles in Series, 40 °C 500 A(400 V) 3 Poles in Series, 55 °C 400 A(400 V) 3 Poles in Series, 70 °C 325 A(600 V) 3 Poles in Series, 40 °C 500 A(600 V) 3 Poles in Series, 55 °C 400 A(600 V) 3 Poles in Series, 70 °C 325 A
connecting capacity auxiliary circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm2Flexible 2x0.75 ... 2.5 mm2Solid 1 x 1 ... 4 mm2Stranded 1 x 1 .... 4 mm2
maximum mechanical switching frequency 300 cycles per hour
maximum operating altitude permissible Without Derating 3000 m
rated impulse withstand voltage (uimp) Main Circuit 8 kV
resistance to shock acc. to iec 60068-2-27 Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 500 A