AM300-30-11 110-125V 50/60Hz / DC Contactor

Description

A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Magnetically latch, control voltage 110-125 V, AC/DC latch
  • Low Voltage Products and Systems
  • Control Products
  • Contactors
  • Block Contactors
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 4-5 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight5.4 KG / psc.
Commodity number85364900
Country of originSE
Dimensions (WxHxD)164x227x180.5 mm
EAN code7320500356920
Product groupSC
eclass V11.0 : 27371003
etim 4 EC000066 - Magnet contactor, AC-switching
etim 5 EC000066 - Magnet contactor, AC-switching
etim 6 EC000066 - Power contactor, AC switching
etim 7 EC000066 - Power contactor, AC switching
etim 8 EC000066 - Power contactor, AC switching
unspsc 39121529
rohs status Following EU Directive 2011/65/EU
operate time Between Coil De-energization and NC Contact Closing 40 ... 50 msBetween Coil De-energization and NO Contact Opening 43 ... 53 msBetween Coil Energization and NC Contact Opening 45 ... 85 msBetween Coil Energization and NO Contact Closing 50 ... 90 ms
terminal type Main Circuit: Bars
gl certificate https://library.abb.com/d/GL_20262-04HH
coil consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 10 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 470 V·APull-in at Max. Rated Control Circuit Voltage DC 520 W
rina certificate https://library.abb.com/d/ELE060313XG/002
rmrs certificate https://library.abb.com/d/RMRS_12-03683-315
rohs information https://library.abb.com/d/2CMT2015-005436
rated frequency (f) Main Circuit 50 / 60 Hz
degree of protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
coil operating limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
mechanical durability 5 million
ambient air temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... +70 °C
horsepower rating ul/csa (200 V AC) Three Phase 100 hp(208 V AC) Three Phase 100 hp(220 ... 240 V AC) Three Phase 100 hp(440 ... 480 V AC) Three Phase 250 hp(550 ... 600 V AC) Three Phase 300 hp
environmental information https://library.abb.com/d/1SFC101063D0201
maximum breaking capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A
rated operational voltage Main Circuit 690 V
number of main contacts nc 0
number of main contacts no 3
object classification code Q
rated making capacity ac-3 10 x Ie AC-3
rated breaking capacity ac-3 8 x Ie AC-3
rated insulation voltage (ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
declaration of conformity - ce https://library.abb.com/d/2CMT2015-005436
number of auxiliary contacts nc 1
number of auxiliary contacts no 1
connecting capacity main circuit Bar 32 mm2Rigid Al-Cable 120 ... 240 mm2Rigid Cu-Cable 16 ... 240 mm2
declaration of conformity - ukca https://library.abb.com/d/2CMT2020-006118
maximum operating voltage ul/csa Main Circuit 600 V
short-circuit protective devices gG Type Fuses 500 A
data sheet, technical information https://library.abb.com/d/1SBC100192C0206
rated operational power ac-3 (pe) (415 V) 160 kW(440 V) 160 kW(500 V) 200 kW(690 V) 250 kW(380 / 400 V) 160 kW(220 / 230 / 240 V) 90 kW
idea granular category code (igcc) 4755 >> Contactors
rated control circuit voltage (uc) 50 Hz 110 ... 125 V60 Hz 110 ... 125 VDC Operation 110 ... 125 V
rated operational current ac-1 (ie) (690 V) 40 °C 500 A(690 V) 55 °C 400 A(690 V) 70 °C 325 A
rated operational current ac-3 (ie) (415 V) 55 °C 300 A(440 V) 55 °C 280 A(500 V) 55 °C 280 A(690 V) 55 °C 280 A(380 / 400 V) 55 °C 305 A(220 / 230 / 240 V) 55 °C 305
rated operational current dc-1 (ie) (110 V) 2 Poles in Series, 40 °C 450 A(220 V) 3 Poles in Series, 40 °C 450 A
rated operational current dc-3 (ie) (110 V) 2 Poles in Series, 40 °C 450 A(220 V) 3 Poles in Series, 40 °C 450 A
rated operational current dc-5 (ie) (110 V) 2 Poles in Series, 40 °C 450 A(220 V) 3 Poles in Series, 40 °C 450 A
connecting capacity auxiliary circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm2Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm2Flexible 2x0.75 ... 2.5 mm2Solid 2 x 1 ... 4 mm2Stranded 2 x 1 .... 4 mm2
maximum electrical switching frequency (AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour
maximum mechanical switching frequency 300 cycles per hour
maximum operating altitude permissible Without Derating 3000 m
rated impulse withstand voltage (uimp) Main Circuit 8 kV
resistance to shock acc. to iec 60068-2-27 Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
conventional free-air thermal current (ith) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 500 A
rated short-time withstand current low voltage (icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2400 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1100 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 3500 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1500 A
connecting terminals (delivered in open position) main poles Flat type c/w screws and bolts