Product type: CP-S.1 24/5.0

CP-S.1 24/5.0 Power supply In:100-240VAC/100-250VDC Out:DC 24V/5A

RoHS Compliant

Description

The CP-S.1 24/5.0 is a power supply from the new generation CP-S.1 range. The primary switch mode power supply offers a wide range input of 85-264 V AC and 90-277 V DC, rated input voltage is 100-240 V AC, respectively 100-250 V DC. The rated output power is 120 W, rated output current is 5 A at an output voltage of 24 V DC. The output voltage is adjustable within a range of 24 to 28 V DC. The power supply provides a U/I output characteristic with a power reserve of up to 150 % for 5 s and allows parallel operation to increase capacity and to enable redundancy. Further features are: power factor correction acc. to EN 61000-3-2. Redundancy unit and buffer modules are available as accessories. CP-S.1 24/5.0
  • Low Voltage Products and Systems
  • Control Products
  • Power Supplies
  • CP-S.1
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.69 KG / psc.
Commodity number85044095
Country of originCN
Dimensions (WxHxD)64x169x155 mm
EAN code4013614561108
Product groupEA
eclass V11.0 : 27040701
etim 5 EC002540 - DC-power supply
etim 6 EC002540 - DC-power supply
etim 7 EC002540 - DC-power supply
etim 8 EC002540 - DC-power supply
unspsc 39121004
function Switch mode power supply
hold-up time (230 V AC) min. 20 ms
output power 120 W
cb certificate https://library.abb.com/d/CB_DE_2-029510
output current 5 A
wiring diagram https://library.abb.com/d/9AKK107992A8774
dnv certificate https://library.abb.com/d/DNV_TAA0000300
eac certificate https://library.abb.com/d/EAC_RU_C-DE.MO05.B.01459
number of phases 1
pollution degree 2
mounting position 1
tightening torque Input Circuit 0.5 N·mOutput Circuit 1.13 N·m
e-number (finland) 2712887
rated output power 120 W
input voltage (uin) 85 ... 264 V AC90 ... 277 V DC
rated frequency (f) 50 Hz60 HzDC
degree of protection Housing IP20Terminals IP20
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
rated output voltage 24 V DC
output voltage (uout) 24 V DC
typical input current (115 V AC) 1.24 A(230 V AC) 0.67 A
wire stripping length Auxiliary Circuit 7 mmInput Circuit 9 mmOutput Circuit 9 mm
rated frequency limits 45 ... 65 Hz
ambient air temperature Operation -25 ... +70 °CStorage -40 ... +85 °C
characteristic of output U/I characteristic curve with power reserve
tightening torque ul/csa Input Circuit 4.4 in·lbOutput Circuit 4.4 in·lb
environmental information https://library.abb.com/d/1SAC200151H0001
minimum mounting distance Other Device Same Type, Horizontal 30 mmOther Device Same Type, Vertical 50 mm
rated input voltage (uin) 100 ... 240 V AC100 ... 250 V DC
object classification code T
output current maximum (iout) 7.5 A
rated insulation voltage (ui) Input Circuit / Output Circuit 300 VInput Circuit / PE 300 VInput Circuit / Relay Contact 300 VOutput Circuit / PE 50 V
declaration of conformity - ce https://library.abb.com/d/1SVD982043-00
declaration of conformity - ukca https://library.abb.com/d/1SVD982043-10
connecting capacity input circuit Flexible with Ferrule 0.5 ... 4.0 mm2Flexible 0.5 ... 4.0 mm2Rigid 0.5 ... 4 mm2
data sheet, technical information https://library.abb.com/d/1SAC200138H0001
connecting capacity output circuit Flexible with Ferrule 0.5 ... 4.0 mm2Flexible 0.5 ... 4.0 mm2Rigid 0.5 ... 4 mm2
electromagnetic compatibility (emc) Immunity - Class BEmission - Class B
surge immunity acc. to iec 61000-4-5 Level 4 Line-to-Ground 4 kVLevel 4 Line-to-Line 2 kV
maximum operating altitude permissible 5000 m
rated impulse withstand voltage (uimp) Input Circuit / Output Circuit 4 kVInput Circuit / PE 4 kVInput Circuit / Relay Contact 4 kVOutput Circuit / PE 0.8 kVOutput Circuit 0.8 kV
connecting capacity input circuit ul/csa Flexible with Ferrule 20-12 AWGFlexible 20-12 AWGRigid 20-12 AWG
connecting capacity output circuit ul/csa Flexible with Ferrule 20-12 AWGFlexible 20-12 AWGRigid 20-12 AWG
resistance to shock acc. to iec 60068-2-27 30g / 3 shocks / 6 ms
resistance to damp heat acc. to iec 60068-2-30 Test Db: 55°C, 2 cycles
resistance to vibrations acc. to iec 60068-2-6 10-58 Hz, ±0.15 mm; 58-150 Hz, 2g, 10 sweep cycles each axis
electrostatic discharge (esd immunity) acc. to iec 61000-4-2 Level 4 Air Discharge 15 kVLevel 4 Contact Discharge 8 kV
radiated electromagnetic field immunity acc. to iec 61000-4-3 Level 3 10 V/m