ABB

2CCF019953R0001

Product type: S803S-K0.5

S803S-K0.5 High Performance MCB

RoHS Compliant

Description

S803S-K0.5 3 Poles K Characteristic 0.5A 6 kA 400/690 VAC High Performance Circuit Breaker HPCB S803S-K0.5
  • Low Voltage Products and Systems
  • Modular DIN Rail Products
  • High Performance Circuit Breakers HPCBs
  • High Performance Circuit Breakers HPCBs - S800
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.735 KG / psc.
Commodity number85362010
Country of originCH
Dimensions (WxHxD)0.081x0.095x0.083 m
EAN code7612271500191
Product groupAF
cn8 85362020
eclass V11.0 : 27141901
etim 7 EC000042 - Miniature circuit breaker (MCB)
etim 8 EC000042 - Miniature circuit breaker (MCB)
remarks Connection from top and bottomConnecting with CU onlyIP40 in enclosure with coverCage terminal with captive screw
standards IEC/EN 60947-2, IEC/EN 60898-1, UL 1077
power loss 6 Wat Rated Operating Conditions per Pole 2 W
rohs status Following EU Directive 2011/65/EU
terminal type Screw Terminals
weee category 5. Small Equipment (No External Dimension More Than 50 cm)
weee b2c / b2b Business To Business
number of poles 3
actuator marking I / O
housing material Insulation group I, RAL 7035
pollution degree 3
rohs information https://library.abb.com/d/9AKK107680A3903, https://library.abb.com/d/2CCC005083D0202
mounting position Any
tightening torque 3.5 N·m
input voltage type AC/DC
rated current (in) 0.5 A
rated voltage (ur) acc. to IEC 60947-2 690 V ACacc. to IEC 60947-2 375 V DCacc. to IEC 60898-1 400 V AC
built-in depth (t2) 82.5 mm
connecting capacity Flexible 0...50 mm2Rigid 0...70 mm2
rated frequency (f) 50...60 Hz
degree of protection acc. to IEC 60529 IP20
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
overvoltage category IV
accessories available Yes
energy limiting class 3
ambient air temperature Operation -25 ... +60 °CStorage -40 ... +70 °C
tripping characteristic K
recommended screw driver Pozidriv 2
environmental information https://library.abb.com/d/2CCY413207D0203
number of protected poles 3
rated operational voltage acc. to IEC 60947-2 690 V ACacc. to IEC 60947-2 375 V DCacc. to IEC 60898-1 400 V AC
object classification code F
contact position indication ON / OFF / TRIP
rated insulation voltage (ui) acc. to IEC/EN 60664-1 690 V
declaration of conformity - ce https://library.abb.com/d/2CCC005083D0202
rated operational current (ie) 0.5 A
data sheet, technical information https://library.abb.com/d/2CCC413003C0208
interrupting rating acc. to ul1077 (240 V AC) 30 kA(480Y / 277 V AC) 14 kA(600Y / 347 V AC) 6 kA
width in number of modular spacings 4.5
rated impulse withstand voltage (uimp) 8 kV
rated conditional short-circuit current (inc) (400 V) 50 kA
resistance to vibrations acc. to iec 60068-2-6 7 - 13.2 Hz / 1mm13.2 - 100Hz / 0.7gwith load 100% x Ie
rated service short-circuit breaking capacity (ics) (240 / 415 V AC) 40 kA(254 / 440 V AC) 22.5 kA(289 / 500 V AC) 11 kA(400 / 690 V AC) 4 kA(375 V DC) 30 kA
rated ultimate short-circuit breaking capacity (icu) (240 / 415 V AC) 50 kA(254 / 440 V AC) 30 kA(289 / 500 V AC) 15 kA(400 / 690 V AC) 6 kA(375 V DC) 30 kA