ABB

2CCS863002R0407

Product type: S803S-K8-R

S803S-K8-R High Performance MCB

RoHS Compliant

Description

S803S-K8-R 3 Pole K Characteristic Ringlug 8A 50kA 240/415VAC High Performance Circuit Breaker HPCB S803S-K8-R
  • Low Voltage Products and Systems
  • Modular DIN Rail Products
  • High Performance Circuit Breakers HPCBs
  • High Performance Circuit Breakers HPCBs - S800
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.735 KG / psc.
Commodity number85362010
Country of originCH
Dimensions (WxHxD)0.081x0.142x0.083 m
EAN code7612271411626
Product groupAF
cn8 85362020
size 3_modules
eclass V11.0 : 27141901
etim 7 EC000042 - Miniature circuit breaker (MCB)
etim 8 EC000042 - Miniature circuit breaker (MCB)
standards IEC/EN 60947-2, IEC/EN 60898-1, UL 1077
power loss 5.1 Wat Rated Operating Conditions per Pole 1.7 W
rohs status Following EU Directive 2011/65/EU
release type K
frequency (f) 50...60 Hz
terminal type Screw Terminals
weee category 5. Small Equipment (No External Dimension More Than 50 cm)
weee b2c / b2b Business To Business
number of poles 3
actuator marking I / O
options provided Ringlug terminal
pollution degree 3
rohs information https://library.abb.com/d/9AKK107680A3903, https://library.abb.com/d/2CCC005083D0202
dimension diagram https://library.abb.com/d/2CCC413003C0201
eplan catalog tree Electrical engineering / Protection devices / General
input voltage type AC/DC
product net length 81 mm
rated current (in) 8 A
rated voltage (ur) acc. to IEC 60947-2 690 V ACacc. to IEC 60947-2 375 V DCacc. to IEC 60898-1 400 V AC
ambient temperature -25...60 °C
built-in depth (t2) 82.5 mm
connecting capacity Flexible 0...50 mm2Rigid 0...70 mm2
rated frequency (f) 50 ... 60 Hz
degree of protection IP20
overvoltage category III
accessories available Yes
energy limiting class 3
ambient air temperature Operation -25...60 °C
tripping characteristic K
environmental information https://library.abb.com/d/2CCY413207D0203
number of protected poles 3
rated operational voltage acc. to IEC 60947-2 690 V ACacc. to IEC 60947-2 375 V DCacc. to IEC 60898-1 400 V AC
object classification code F
contact position indication ON / OFF / TRIP
rated insulation voltage (ui) acc. to IEC/EN 60664-1 690 V
declaration of conformity - ce https://library.abb.com/d/2CCC005083D0202
rated operational current (ie) 8 A
data sheet, technical information https://library.abb.com/d/2CCC413003C0208
interrupting rating acc. to ul1077 (480Y / 277 V AC) 14 kA(600Y / 347 V AC) 6 kA
width in number of modular spacings 4.5
rated impulse withstand voltage (uimp) 8 kV
rated conditional short-circuit current (inc) (230 V) 50 kA(400 V) 50 kA
rated service short-circuit breaking capacity (ics) (240 / 415 V AC) 40 kA(254 / 440 V AC) 22.5 kA(400 / 690 V AC) 4 kA(375 V DC) 30 kA
rated ultimate short-circuit breaking capacity (icu) (240 / 415 V AC) 50 kA(254 / 440 V AC) 30 kA(400 / 690 V AC) 6 kA(375 V DC) 30 kA(230 V) 50 kA