ABB

2CDH781001R2577

Product type: S751/3DR-K50

S751/3DR-K50 sel. main CB K-Char.,25kA,50A,3x1P

RoHS Compliant

Description

Selective main circuit-breakers of the S 750 DR series are SMCBs based on DIN VDE 0641-21 with voltage-independent operating principle. This means that they do not rely on a control circuit to make or break contact (SHU) and are therefore particularly suitable for use in energy distributionsystems with maximum availability requirements. They offer total selectivity to downstream MCBs and outstanding selectivity to upstream protective devices due to unique current limiting selectivity. S751/3DR-K50
  • Low Voltage Products and Systems
  • Modular DIN Rail Products
  • Selective Main Circuit Breakers SMCBs
  • Selective Main Circuit Breakers SMCBs
  • S750DR
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 6-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight1.05 KG / psc.
Commodity number85369095
Country of originBG
Dimensions (WxHxD)0.027x0.13x0.092 m
EAN code4016779838894
Product groupAE
cn8 8536 90 95
eclass V11.0 : 27141903
etim 7 EC001047 - Selective main line circuit breaker
etim 8 EC001047 - Selective main line circuit breaker
unspsc 39121614
function Single Pole Switching
standards DIN VDE 0641-21
power loss at Rated Operating Conditions per Pole 7.2 W
rohs status Following EU Directive 2011/65/EU
mounting type DIN-Rail
terminal type Screw Terminals
weee category 5. Small Equipment (No External Dimension More Than 50 cm)
weee b2c / b2b Business To Consumer
number of poles 3x1
pole net weight 0.35 kg
actuator marking I / O
options provided 3x 1 poleindividually switching
pollution degree 3
rohs information https://library.abb.com/d/2CDK400642D0201
dimension diagram https://library.abb.com/d/2CDC022023F0011
installation size acc. to DIN 43880 3
mounting position Any
tightening torque 2.5 ... 3 N·m
eplan catalog tree Electrical engineering / Protection devices / Safety switch
i2t characteristic https://library.abb.com/d/9AKK108466A4490
rated current (in) 50 A
connecting capacity Flexible with Ferrule 2.5 ... 50 mm2Flexible 2.5 ... 50 mm2Rigid 2.5 ... 50 mm2Stranded 2.5 ... 50 mm2
rated frequency (f) 50 / 60 Hz
screw terminal type Cable Clamp
certification agency DIN
degree of protection IP20Enclosure with Cover IP40
mounting on din rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
overvoltage category IV
accessories available Yes
suitable for isolation Yes
ambient air temperature Operation -25 ... +55 °CStorage -40 ... +70 °C
dielectric test voltage 50/60 Hz, 1 min: 2 kV
power supply connection Arbitrary
tripping characteristic K (Selective)
environmental conditions 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 %
recommended screw driver Cross Recess Pozidriv 2Slotted 1 x 5.5
rated operational voltage 230 / 400 V AC
object classification code F
contact position indication Red ON / Green OFF
rated insulation voltage (ui) acc. to IEC/EN 60664-1 690 V
declaration of conformity - ce https://library.abb.com/d/2CDK400634D2701
data sheet, technical information https://library.abb.com/d/2CDC415012D0104
time-current characteristic curve https://library.abb.com/d/9AKK108466A4496
rated short-circuit capacity (icn) (230 / 400 V AC) 25 kA
rated impulse withstand voltage (uimp) 6 kVat 2000 m 8 kVat Sea Level 9.8 kV
resistance to shock acc. to iec 60068-2-27 30g / 3 shocks / 11 ms
resistance to vibrations acc. to iec 60068-2-6 2g, 20 cycles at 5 ... 150 ... 5Hz