Measurement and metering transformer cabinet, series A, fully assembled cabinet, Expansion option: Lateral, for the internal use, class of protection II (double insulated), degree of protection IP31, applicable standards: EN 61439-1, Rated operational voltage 415V AC 50/60 Hz, rated current 200 A, Rated current of the assembly of switchgear and controlgear InA 200 A, Powder-coated, in RAL 9016, enclosure out of Sheet steel / Plastic, double door, dimensions in mm (H x W x D): 1100 x 800 x 215, Earthing system TN-S, 5-pole, net side compartment, meter space: with busbar, net side compartment, SG space: with busbar, net side compartment, meter space: with busbar, Meter replacement plate Provision from DSO, Pre-wired from current and voltage pfad up to test terminal X1, voltage path Miniature circuit breaker B6/25 kA 3-pole overvoltage path catagory 3 and motorprotection switch 1-1,6A, busbar system Cu busbars 12 x 5 mm 5-pole, parting point before the current transformer Fuse base element NH2/400 A, current transformer range Mounting plate for Block-CT, parting point after the current transformer Possibility to mount customer switch disconnector ABB OT250/3-polig, primary wiring L1-L3, N 120 qmm, PE 70 qmm, Connection N+PE (M8), Note: Incomer cabinet EK220 recommended, Grid unit 7 GU, Overall height 3, panel width 3, Space units 252, covers out of Plastic, Quick sealable connection, RAL 7035 KS450