| Weight | 0.22 KG / psc. |
| Commodity number | 85363030 |
| Country of origin | IT |
| Dimensions (WxHxD) | 0.035x0.085x0.069 m |
| EAN code | 8012542341758 |
| Product group | AM |
| cn8 | 85363030 |
| eclass | V11.0 : 27142201 |
| etim 7 | EC000003 - Residual current circuit breaker (RCCB) |
| etim 8 | EC000003 - Residual current circuit breaker (RCCB) |
| standards | IEC/EN 61008 |
| cable size | 25 mm2 |
| power loss | 3.60 W |
| mounting type | on DIN rail EN 60715 (35mm) by means of mounting clip |
| terminal type | Screw Terminals |
| weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| accessory type | Auxiliary contact, Signal contact/auxiliary contact, Shunt trip, Undervoltage release, Overvoltage release, Motor operating device, Auto reclosing unit |
| weee b2c / b2b | Business To Consumer |
| impulse current | I (max, 8 / 20 μs) 3000 A |
| number of poles | 2 |
| options provided | None |
| pollution degree | 3 |
| rohs information | https://library.abb.com/d/9AKK106713A5610 |
| e-number (sweden) | 2160154 |
| mounting position | Any |
| test voltage (ut) | 170-253 V AC |
| tightening torque | 2.8 N·m |
| e-number (finland) | 3214062 |
| input voltage type | AC |
| rated current (in) | 40 A |
| rated voltage (ur) | 230 V |
| built-in depth (t2) | 69 mm |
| connecting capacity | Busbar 10 mm2Flexible 1 ... 25 mm2Stranded 1 ... 25 mm2 |
| delay time (τ) | 10 ms |
| number of batteries | 0 |
| rated cross-section | 1 - Solid-Core 1 ... 25 mm2 |
| rated frequency (f) | 50 / 60 Hz |
| screw terminal type | Failsafe Bi-directional Cylinder-lift Terminal |
| degree of protection | Housing IPX4Terminals IP2X |
| electrical endurance | 10000 cycle |
| overvoltage category | III |
| accessories available | Yes |
| maximum surge current | 3 kA |
| wire stripping length | 12 mm |
| rated residual current | 300 mA |
| ambient air temperature | Operation -25 ... +70 °C |
| dielectric test voltage | 2500 V |
| environmental conditions | 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 % |
| operating characteristic | Instantaneous (APR High Immunity) |
| type of residual current | B type |
| rated operational voltage | 230 V |
| object classification code | Q |
| mechanical endurance (nendu) | 20000 cycle |
| rated insulation voltage (ui) | 440 V |
| declaration of conformity - ce | https://library.abb.com/d/9AKK106713A5610 |
| data sheet, technical information | https://library.abb.com/d/9AKK107991A7569 |
| width in number of modular spacings | 2 |
| rated impulse withstand voltage (uimp) | 4 kV |
| environmental product declaration - epd | https://library.abb.com/d/9AKK108467A3700 |
| number of modular spacings per din rail | 2 |
| resistance to shock acc. to iec 60068-2-27 | 25g / 2 shocks / 13 ms |
| rated residual breaking capacity (iδm) | 1 kA |
| rated conditional short-circuit current (inc) | 10 kA |
| resistance to vibrations acc. to iec 60068-2-6 | 0.1 mm or 1 g - 20 cycles at 5...150...5 Hz |