| Weight | 0.075 KG / psc. |
| Commodity number | 85369095 |
| Country of origin | BG |
| Dimensions (WxHxD) | 0.018x0.057x0.067 m |
| EAN code | 3660308525352 |
| Product group | AK |
| cn8 | 85363090 |
| eclass | V11.0 : 27130805 |
| etim 7 | EC000941 - Surge protection device for power supply systems |
| etim 8 | EC000941 - Surge protection device for power supply systems |
| version | Plug-in |
| fuse size | 4 modular spacing |
| standards | IEC 61643-11 / EN 61643-11 |
| power loss | 28 mW |
| suitable for | To protect the systems against the transient overvoltage (lightning) |
| mounting type | DIN rail (top hat rail) 35 mm |
| weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| arrester class | II |
| weee b2c / b2b | Business To Business |
| cqc certificate | https://library.abb.com/d/9AKK107680A1974 |
| impulse current | I (imp, 10 / 350 μs) 2 kA |
| number of poles | 1 |
| options provided | Replacement Cartridge |
| status indicator | Yes |
| discharge current | Nominal 20 kAMaximum 4 kANominal (8 / 20 μs) 20 kAI (max, 8 / 20 μs) 40 kA |
| voltage rating dc | 350 V |
| rated voltage (ur) | 230 V AC |
| degree of protection | IP20 |
| number of conductors | 1 |
| transmission standard | Optic |
| number of protected poles | 1 |
| object classification code | 141DCC |
| short circuit withstand icc | 100 kA |
| declaration of conformity - ce | https://library.abb.com/d/9AKK108466A4617 |
| preventive maintenance feature | Yes |
| voltage protection level ( up) | 1.4 kV(L-N) 1.4 kV(N-PE) 1.4 kV(L-PE) 1.4 kV |
| data sheet, technical information | https://library.abb.com/d/No document needed |
| width in number of modular spacings | 1 |
| nominal ac voltage of the system (uo) | 230 / 400 V |
| temporary overvoltage test value (ut) | 337 V |
| maximum operating altitude permissible | Without Derating 5000 |
| type of low voltage distribution system | TTTN-CTN-S |
| maximum continuous operating voltage (uc) | (L-PE) 275 V(L-L) 275 V(L-N) 275 V(N-PE) - V |
| rated service short-circuit breaking capacity (ics) | 100 kA |