| Weight | 1.2 KG / psc. |
| Commodity number | 85369095 |
| Country of origin | BG |
| Dimensions (WxHxD) | 0.142x0.096x0.077 m |
| EAN code | 3660308525116 |
| Product group | AK |
| cn8 | 85363090 |
| eclass | V11.0 : 27130808 |
| etim 7 | EC001457 - Combined arrester for power supply systems |
| etim 8 | EC001457 - Combined arrester for power supply systems |
| version | Plug-in |
| fuse size | 8 modular spacing |
| standards | IEC 61643-11 / EN 61643-11 |
| power loss | 121 mW |
| declaration | https://library.abb.com/d/2CTC432056G1701 |
| suitable for | To protect the systems against the transient overvoltage (lightning) |
| mounting type | DIN rail (top hat rail) 35 mm |
| weee category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| arrester class | III |
| weee b2c / b2b | Business To Business |
| cqc certificate | https://library.abb.com/d/9AKK107680A1975 |
| eac certificate | https://library.abb.com/d/2CTC436008G1701 |
| impulse current | I (imp, 10 / 350 μs) 12.5 kAI (total, 10 / 350 μs) 50 kA |
| number of poles | 4 |
| options provided | Industry, commercial building |
| status indicator | Yes |
| discharge current | Nominal 20 kAMaximum 80 kATotal 320 kA |
| voltage rating dc | 560 V |
| mechanical drawings | https://library.abb.com/d/2CTC800015F2900.pdf, https://library.abb.com/d/2CTC800015F2901.dxf, https://library.abb.com/d/2CTC800015F2902.stp, https://library.abb.com/d/2CTC800015F2903.igs |
| degree of protection | IP20 |
| auxiliary circuit load | Minimum 12Vdc - 10mAMaximum 250Vac - 1A |
| lightning impulse current | 12,5 |
| number of protected poles | 4 |
| object classification code | 141BEC |
| short circuit withstand icc | 100 kA |
| position of neutral terminals | Right |
| declaration of conformity - ce | https://library.abb.com/d/9AKK108466A4617 |
| preventive maintenance feature | Yes |
| voltage protection level ( up) | (L-N) 3.8 kV(N-PE) 1.9 kV(L-PE) 1.9 kV |
| number of auxiliary contacts nc | 1 |
| number of auxiliary contacts no | 1 |
| short-circuit protective devices | Curve B Breakers ≤ 125 ACurve C Breakers ≤ 125 AgL Type Fuses ≤ 160 AgG Type Fuses ≤ 160 A |
| data sheet, technical information | https://library.abb.com/d/2CTC431056D0201 |
| width in number of modular spacings | 8 |
| nominal ac voltage of the system (uo) | 400 / 690 V |
| temporary overvoltage test value (ut) | 581 V |
| maximum operating altitude permissible | Without Derating 5000 |
| type of low voltage distribution system | TN-SIT |
| maximum continuous operating voltage (uc) | (L-PE) 440 V(L-L) 760 V(L-N) 760 V(N-PE) 440 V |
| follow current extinction capacity if (i fi) | (L-N) - kA(N-PE) - kA |