KEYENCE

FD-EPH5

Product type: FD-EPH5

Sensor head Outer diameter of pipe 3/16”

  • Process Controls / Process Sensors
  • Flow Sensors / Flow Meters
  • Air Flow and Pressure Dual Sensor
  • Models
  • Sensor head Outer diameter of pipe 3/16”
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: by agreement
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.128 KG / psc.
Commodity number
Country of origin
Dimensions (WxHxD)
EAN code
Product group
Model FD-EPH5
Nylon 4.76 ±0.1 mm 0.19" ±0.004"
Pipe materials Resin pipe connectible to a one-touch coupling
Supported gases Air, nitrogen, argon, and non-corrosive gases *2
Supported gas temperature −10°C to +60°C 14 to 140°F
Pressure resistance 1 MPa
Flow rate detection principle Ultrasonic transmission time difference method
(20°C 68°F , atmospheric pressure conversion) * Initial display Gas at 20°C 68°F , 0.0 MPa
Gas at 20°C 68°F , 02 MPa 90 L/min 3.18 CFM
Gas at 20°C 68°F , 04 MPa 150 L/min 5.30 CFM
Gas at 20°C 68°F , 06 MPa 210 L/min 7.41 CFM
Measurement accuracy ±(2.0% of RD+1.0% of F.S.) *3 *4
Repeatability Response time of 2.5 ms: ±0.4% of F.S.
Overall accuracy ±2.0% of F.S. *3
Accumulated flow 0.01/0.1/1/10/100 L
Pressure 0.1/1 kPa
Ambient temperature −10°C to +60°C 14 to 140°F (no freezing)
Relative humidity 35%RH to 85%RH (no condensation)
Vibration resistance 10 to 500 Hz, power spectral concentration: 0.816 G 2 /Hz, XYZ axes
Shock resistance 100 m/s 2 , 16 ms pulse, XYZ axes, 1000 times for each axis
Flow channel (parts that contact the gas) PBT/Brass electroless nickel plating/NBR/nylon
Outer diameter of pipe 3/16” (Approx. 4.76 mm 0.19" ) *1
Polyurethane 4.76 ±0.15 mm 0.19" ±0.006"
Rated pressure −100 kPa to +0.75 MPa * However, the flow rate cannot be measured in the range of −100 to −50 kPa.
Instantaneous flow 0.01/0.1 L/min
Enclosure rating IP65 (IEC60529)
Sensor unit (parts that do not contact the gas) PBT/PAR/iron/Brass electroless nickel plating/POM/NBR/stainless steel
We’re sorry, our website no longer supports