| Weight | 1.5 KG / psc. |
| Commodity number | 85044082 |
| Country of origin | CZ |
| Dimensions (WxHxD) | 110x124x127 mm |
| EAN code | 875404003045 |
| Product group | A-Standard |
| Derating | 20W/°C for +55 to +70°C |
| m_features | 3AC 380-480V Wide-range input; Communication interface: IO-Link v 1.1 (IEC 61131-3); 4-pole M12 connector; Width only 110mm; 95.3% Full load and excellent partial load efficiencies; 50% BonusPower, 1440W for up to 5s; 110A Peak current for 25ms for easy fuse trippin; Active power factor correction (PFC); Negligibly low input inrush current; Full power between -25°C and +60°C; Transmission speed: COM3 (< 230.4 kBaud); Integrated 8 kbit EEPROM for automated parameterization; Remote control of output voltage and remote shut-down via IO-Link possible, if required |
| DC-OK signal | yes |
| Output power | 960W |
| Power factor | 0.92 |
| Output current | 34.3A at 28V; 40A at 24V |
| Packaging unit | 1 pc |
| Power reserves | 50% BonusPower |
| Product status | Lead time on request |
| Mounting method | DIN rail |
| Nominal voltage | 24Vdc |
| AC Input voltage | AC 380 - 480V |
| Adjustment range | 24 - 28V |
| E classification | eClass 5.1 27049002; eClass 6.x 27049002; eClass 7.x 27049002; eClass 8.0 27049002; eClass 9.0 27040701; ETIM 4.0 EC000599; ETIM 5.0 EC002540 |
| Efficiency, typ. | 95.3% |
| Connection method | Screw terminals |
| Power losses, typ. | 47.3W |
| Harmonic correction | active |
| Input inrush current | 4.5A / 4.5A |
| Output current range | 40 - 34.3A |
| Operating temp. range | -25°C to 70°C |
| Warranty period (months) | 36 |
| MTBF SN 29500 @ 40°C (h) | 685000h |
| Ripple and noise voltage max. | 100mVpp |
| Input inrush current limitation | active |
| Weight per unit (excl. packaging) | 1500g |
| External input fuse recommendation | B-6A / C-6A |