Rittal

3185730

Product type: SK 3185730

SK roof-mounted cooling unit Blue e+, carbon steel, cooling module, 4436 BTU/h 110-240 V, 1~, 50/60 Hz, 380-480 V, 3~, 50/60 Hz, WHD: 700 x 308 x 560 mm

Description

Revolutionary energy efficiency through innovative hybrid technology. Average 75% energy saved due to speed-regulated components and heat pipe technology. Unique multi-voltage capability for worldwide use. Intuitive operation via touch display.
  • Climate Control
  • Cooling units, thermoelectric coolers
  • Roof-mounted Blue e cooling unit Total cooling output 4435.78 BTU/h
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: by agreement
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight56.25 KG / psc.
Commodity number84158200
Country of origin
Dimensions (WxHxD)700x308x560 mm
EAN code4028177927155
Product groupSK
Version roof-mounted
Benefits An average of 75% energy savings due to speed-regulated components and heat pipe technology
Material Carbon steel
Color RAL 7035
Supply includes Roof-mounted Blue e+ cooling unit Pleated filter Wired ready for connection Assembly components Condensate hose (3 m)
Options For remote monitoring and networking of cooling units and chillers, use the Blue e+ Generation IoT Interface, item number 3124.300. Increase machine availability and process safety by remote monitoring of device data, condition, and system messages.
Total cooling output to DIN EN 14511 Cooling output L35 L35/50 Hz: 1.3 kW Cooling output L35 L35/60 Hz: 1.3 kW Cooling output L35 L50/50 Hz: 0.6 kW Cooling output L35 L50/60 Hz: 0.6 kW ( Cooling output L35 L35/50 Hz: 4,436 BTU/h Cooling output L35 L35/60 Hz: 4,436 BTU/h Cooling output L35 L50/50 Hz: 2,047 BTU/h Cooling output L35 L50/60 Hz: 2,047 BTU/h )
Rated operating voltage 110 V - 240 V, 1~, 50 Hz/60 Hz
Note Can be mounted on enclosures with 800 x 600 mm (W x D) minimum dimensions
Rated output 0.75 kW
Air throughput (unimpeded air flow) External circuit: 750 m³/h Internal circuit: 700 m³/h ( External circuit: 441.4 cfm Internal circuit: 412 cfm )
Energy efficiency ratio (EER) 50/60 Hz L35 L35 Refrigeration factor L35 L35 (EER) 50 Hz: 2.04 Refrigeration factor L35 L35 (EER) 60 Hz: 2.04
Seasonal energy efficiency ratio (SEER) 50/60 Hz 5.3
Dimensions Width: 700 mm Height: 308 mm Depth: 560 mm ( Width: 27.6 ˝ Height: 12.1 ˝ Depth: 22 ˝ )
Protection category IP to EN 60 529 External circuit IP 54 with pleated filter
Refrigerant/cooling medium Refrigerant: R-513A Quantity: 0.6 kg Global Warming Potential (GWP): 631 CO₂ equivalent (CO₂e): 0.38 t ( Refrigerant: R-513A Quantity: 1.3 lb. )
Type of connection (electrical) Plug-in terminal strip
Temperature control e+ controller (factory setting +35 °C)
Operating temperature range -20 °C...55 °C ( -4 °F...131 °F )
Storage temperature range -40 °C...70 °C ( -40 °F...158 °F )
Operating temperature range of refrigerant circuit (active) 3 °C...55 °C
Operating temperature range of heat pipe -20 °C...45 °C
Setting range 20 °C...50 °C ( 68 °F...122 °F )
Rated power Pel Rated power L35 L35/50 Hz: 0.67 kW Rated power L35 L35/60 Hz: 0.67 kW Rated power L35 L50/50 Hz: 0.57 kW Rated power L35 L50/60 Hz: 0.57 kW
Permissible operating pressure (p max) 24 bar ( 348.1 PSI )
Net weight 49 kg
ETIM 9 EC000855
ETIM 8 EC000855
ECLASS 80 27180704