Rittal

3313290

Product type: SK 3313290

LCP Rack DX, 68243 BTU/h, flush, RAL 7035, WHD: 300 x 2000 x 1200 mm, 380 – 480 V/3~/50 – 60 Hz

Description

Rack-based cooling of one to two IT racks. Continuous adjustment of the cooling output provided by output-controlled compressors in the Rack DX LCP (evaporator). An external condenser is required to operate the unit.
  • IT Infrastructure
  • IT Cooling Solutions
  • Liquid Cooling Package
  • Liquid Cooling Package LCP Rack DX
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: by agreement
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight261 KG / psc.
Commodity number84186900
Country of origin
Dimensions (WxHxD)300x2000x1200 mm
EAN code4028177953819
Product groupSK
Version Rack cooling
Benefits Maximum energy efficiency due to EC fan technology and IT-based control
Applications Ideal for IT cooling of small and medium-sized locations
Function principle The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
Material Carbon steel, spray finished
Options Humidifier
Monitoring Direct connection of the unit via SNMP over Ethernet
Total cooling output to DIN EN 14511 Useful cooling output L22 L35: 20 kW
Total cooling output/number of fan modules 20 kW/4 ( 68,243 BTU/h )
Modulation range 5 ‐ 20 kW
Air throughput (unimpeded air flow) At 50 Hz: 4,800 m³/h ( At 50 Hz: 2,825.2 cfm )
Dimensions Width: 300 mm Height: 2,000 mm Depth: 1,200 mm ( Width: 11.8 ˝ Height: 78.7 ˝ Depth: 47.2 ˝ )
Suitable for enclosure type VX IT
Installation in bayed enclosure suite Flush
Rated operating voltage 380 V - 480 V, 3~, 50 Hz/60 Hz
Rated current max At 50 Hz: 12.4 A
Max cooling output 20 kW ( 68,243 BTU/h )
Type of connection (electrical) Connection clamp
Duty cycle 100 %
EC fan Yes
SNMP card Yes
Fans may be exchanged with the system operational Yes
Temperature control Infinitely variable fan control
Start-up current 32 A
Operating temperature range 5 °C...35 °C ( 41 °F...95 °F )
Noise pressure level At 50 Hz: 68 dB(A)
Protection category IP to EN 60 529 IP 20
Net weight 250 kg
ETIM 9 EC002515
ETIM 8 EC002515
ECLASS 80 27180712