Rittal

3320600

Product type: SK 3320600

SK Chiller TopTherm, Stand alone, open, 8872/11260 BTU/h, 400-460 V, 3~, 50/60 Hz, WHD: 602 x 676 x 645 mm

Description

TopTherm chillers in roof-mounted or stand-alone versions are flexible and compact. They offer centralized and efficient cooling of the cooling water and supply air/water heat exchangers and other devices. With nano-coated condenser as standard.
  • Climate Control
  • Air-water heat exchangers, chillers
  • Chillers
  • TopTherm chillers 3412.1 - 13,648 BTU/h
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: by agreement
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight98 KG / psc.
Commodity number84186900
Country of origin
Dimensions (WxHxD)
EAN code4028177351172
Product group
Version Compact, modular layout of the refrigeration components Pump to convey the medium
Benefits Precise temperature control, based on microprocessor technology
Color RAL 7035
Supply includes Condenser with hydrophobic RiNano coating Complete unit ready for connection Multilingual documentation including functional diagram and wiring plans
Protection category IP to EN 60 529 IP 44 (electrics)
Total cooling output Tw10 / Tu32 Cooling output Tw10 Tu32/50 Hz: 2.7 kW Cooling output Tw10 Tu32/60 Hz: 3 kW ( Cooling output Tw10 Tu32/50 Hz: 9,213 BTU/h Cooling output Tw10 Tu32/60 Hz: 10,236 BTU/h )
Total cooling output Tw18 / Tu32 Cooling output Tw18 Tu32/50 Hz: 3 kW Cooling output Tw18 Tu32/60 Hz: 3.4 kW ( Cooling output Tw18 Tu32/50 Hz: 10,236 BTU/h Cooling output Tw18 Tu32/60 Hz: 11,601 BTU/h )
Total cooling output to DIN EN 14511 Tw18 / Tu35 Cooling output Tw18 Tu35/50 Hz: 2.6 kW Cooling output Tw18 Tu35/60 Hz: 3.3 kW
Air throughput (unimpeded air flow) At 50 Hz: 1,785 m³/h At 60 Hz: 1,785 m³/h ( At 50 Hz: 1,050.6 cfm At 60 Hz: 1,050.6 cfm )
Rated operating voltage 400 V, 3~, 50 Hz
Dimensions Width: 602 mm Height: 676 mm Depth: 645 mm ( Width: 23.7 ˝ Height: 26.6 ˝ Depth: 25.4 ˝ )
Temperature control Microcontroller control (factory setting +20 °C)
Operating temperature range 10 °C...43 °C ( 50 °F...109 °F )
Operating temperature range of cooling medium 10 °C...30 °C ( 50 °F...86 °F )
Temperature hysteresis ± 2 K
Refrigerant/cooling medium Refrigerant: R-513A Quantity: 1.2 kg Global Warming Potential (GWP): 631 CO₂ equivalent (CO₂e): 0.75 t ( Refrigerant: R-513A Quantity: 2.6 lb. )
Volumetric flow (cooling medium) At 50 Hz: 20 l/min
Rated power Pel At 50 Hz: 2.03 kW At 60 Hz: 2.67 kW
Rated current max At 50 Hz: 4.05 A At 60 Hz: 4.35 A
Refrigeration factor (EER) 50 Hz Tw18 / Tu35 DIN EN 14511 2.53
Water circuit Open
Water connections G ½" internal thread
Number of cooling circuits 1
Tank Material: Plastic PP Volume: 30 l
Net weight 88 kg
ETIM 9 EC002516
ETIM 8 EC002516
ECLASS 80 27180713