Technical data †- 18 single-channel or optionally 9 dual-channel digital safety inputs (PL e to EN ISO 13849-1) †- 2 single-channel analogous safety inputs, 0 … 10 V, 4 … 20 mA (PL d to EN ISO 13849-1) †- 2 single-channel or optionally 1 dual-channel p-type safety semi-conductor output and - 2 p- and n-type dual-channel semi-conductor outputs (24 VDC / 1.8 A, PL e to EN ISO 13849-1) †- 2 single-channel or optionally 1 dual-channel safety relay output 50 V / 6 A; PL e to EN ISO 13849-1) †- 4 single-channel signalling outputs (0.1 A); together with safety inputs †- 3 cyclic outputs (0.1 A) †- Status and diagnosis through OLED display -† Status of the inputs and outputs †- Plain text error messages -† Programme selection through toggle switches, input of additional functions also through toggle switches †- LED’s for UB, RUN, ERROR †- Dimensions: width x height x depth: 52.5 × 100 × 118 mm †- PL e (EN ISO 13849-1); SIL 3 (IEC 62061)