Schneider Electric

18683

Product type: 18683

Residual current circuit breaker (RCCB), Acti9 RED, 2P, 40A, A type, 30mA

Description

This Acti9 REDs is a modular residual current circuit breaker (RCCB) with recloser. It is a 2P circuit breaker with 40A In rated current, 30mA earth leakage sensitivity and A type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. It disconnects of on-load electric circuits already protected against overloads and short-circuits. It restarts automatically after insulation monitoring of the downstream circuit. It is only used on TT and TN-S earthing grounding systems. The Acti9 RED version is dedicated to residential applications. This product is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 630A. The (Inc/IΔc) conditional rated short circuit current is 6kA. It has a mechanical endurance going up to 1000 cycles. The Ue operational voltage is 230VAC. The Ui rated insulation voltage is 500VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The dimensions are (W) 71mm x (H) 115mm x (D) 79.5mm. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is from -5°C to 40°C. The storage temperature is from -20°C to 60°C.
  • Low Voltage Products and Systems
  • Electrical Protection and Control
  • Acti9 Residual Current Devices - RCDs
  • RED - Recloser
Contact Person
Thomas Hoffmann
+49 305 201 4443
sales@zwodltd.com
Payment
Bank TransferVisaMastercardPayPal
Worldwide shipping
DHLUnited Parcel ServiceFedEx ExpressTNT ExpressDB Schenker
Additional Information
Price: Please send request
Request Lead Time: app. 1 Day
Delivery Time: app. 8-9 Weeks
Estimated delivery time to our warehouse in Berlin
Delivery Terms: FCA Berlin
individually for each client according to INCOM TERMS 2025
Multiples Of: 1
Product Specifications
Product AttributeAttribute Value
Weight0.429 KG / psc.
Commodity number
Country of originPT
Dimensions (WxHxD)110x110x125 mm
EAN code
Product group
range of product Acti9
Product name Acti9 RED
Product or component type Residual current circuit breaker (RCCB)
Device short name RED
Protection type Recloser
Poles description 2P
Neutral position Left
[In] rated current 40 A
Earthing system TN-S TT
Network type AC
Earth-leakage sensitivity 30 mA
Device location in system Outgoer
Network frequency 50 Hz
[Ue] rated operational voltage 230 V AC 50 Hz phase to neutral
Reset Fault reset earth leakage
Test function Manual at > 100 V
Earth-leakage protection time delay Instantaneous
Earth-leakage protection class Type A
Minimum leakage resistance 70 kOhm at operating 20 kOhm at non-operating
[Im] rated making and breaking capacity Idm 630 A 230 V
Rated conditional short-circuit current Inc: 6 kA - associated with DPN, 40 A Inc: 6 kA - associated with DPNN, 40 A Inc: 10 kA - associated with iC60N, 25 A Inc: 10 kA - associated with iC60H, 25 A Inc: 10 kA - associated with iC60L, 25 A Inc: 6 kA - associated with iC60N, 40 A Inc: 6 kA - associated with iC60H, 40 A Inc: 6 kA - associated with iC60L, 40 A Inc: 10 kA - associated with NG125, 25 A Inc: 6 kA - associated with NG125, 40 A Inc: 10 kA - associated with gG fuse, 25 A Inc: 6 kA - associated with gG fuse, 40 A
[Ui] rated insulation voltage 500 V
[Uimp] rated impulse withstand voltage 4 kV
Surge current 250 A
Control type Toggle
Local signalling 1 red LED Recloser : ON/OFF indication Residual current device : ON/OFF indication
Operating mode Reclosing time: 90 s Maximum operational frequency: 15/hour Max nb of consecutive restart: 3 Min interval between 2 closings: 180 s Insulation fault presence monitoring Stopping restart cycle if insulation fault present Restart in event of transient insulation fault
Mounting mode Fixed
Mounting support 35 mm symmetrical DIN rail
9 mm pitches 8
Height 115 mm
Width 71 mm
Depth 79.5 mm
Mechanical durability 1000 cycles open-close
Connections - terminals Guard tunnel terminal 35 mm² rigid Guard tunnel terminal 25 mm² flexible
Auxiliary connection terminal Tunnel type terminal in 2.5 mm² flexible Tunnel type terminal in 2.5 mm² rigid
Wire stripping length 12 mm
Tightening torque 2 N.m
Standards EN/IEC 63024
IP degree of protection IP20
Pollution degree 2
Electromagnetic compatibility 8/20 µs wave immunity, 250 A
Tropicalisation 2
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -5…40 °C
Ambient air temperature for storage -20…60 °C
Unit Type of Package 1 PCE
Package 1 Height 11 cm
Package 1 Width 11 cm
Package 1 Length 12.5 cm
Package 1 Weight 429.333 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 2 Weight 5.623 kg
Unit Type of Package 3 P12
Number of Units in Package 3 96
Package 3 Height 50 cm
Package 3 Width 80 cm
Package 3 Length 120 cm
Package 3 Weight 56.984 kg
Warranty (in months) 18
Packaging made with recycled cardboard information_stroke Recycled cardboard content is minimum 70% (50% in US) Some orders may include non-recycled cardboard until stock runs out Yes
Repair information_stroke Repair services are offered by Schneider Electric No
Take-back information_stroke Whether the product has been included in a global take-back program Some products are eligible in some geographies, please verify if it's available in your country No
Instruction sheet https://download.se.com/files?p_enDocType=Instruction+sheet&p_File_Name=QGH4059601-01.pdf&p_Doc_Ref=QGH4059601
We’re sorry, our website no longer supports
For your security and a speedy zwod experience, please update your browser: