| Weight | 0.122 KG / psc. |
| Commodity number | |
| Country of origin | |
| Dimensions (WxHxD) | |
| EAN code | |
| Product group | |
| Number of Poles : | 1 |
| Current Rating (IEC) (A): | 125 |
| Current Rating (UL) (A): | 115 |
| Number of Positions : | 8 |
| Contact Current Rating (Max) (A): | 125 |
| Block Function : | Feed-Through |
| Number of Circuits : | 1 |
| Number of Poles - Main Circuit : | 1 |
| Number of Poles - Output 1 : | 1 |
| Number of Poles - Output 2 : | 6 |
| Number of Levels : | 1 |
| Short Circuit Current Rating (kA): | 100 |
| Short-Time Withstanding Current Rating @ 1s (A): | 4200 |
| Voltage Rating (IEC) (VAC): | 1000 |
| Voltage Rating (IEC) (VDC): | 1500 |
| Voltage Rating (CSA) (V): | 1000 |
| Dielectric Withstanding Voltage (Max) (V): | 2200 |
| Input Current (Max) (A): | 125 |
| Impulse Withstanding Voltage Rating (IEC) (V): | 8000 |
| Operating Voltage Rating (UL & CSA) (Max) - Main Circuit (V): | 1000 |
| Peak Withstanding Current Rating (kA): | 30 |
| Power Loss (W): | 4 |
| Primary Product Color : | Gray |
| Termination Method to Wire & Cable : | Screw |
| Tightening Torque - Output 1 (in-lbs): | 18 – 26.5 |
| Tightening Torque - Output 1 (Nm): | 2 – 3 |
| Tightening Torque - Main Circuit (in-lbs): | 31 – 44 |
| Tightening Torque - Main Circuit (Nm): | 3.5 – 5 |
| Tightening Torque - Output 2 (Nm): | 2 – 3 |
| Tightening Torque - Output 2 (in-lbs): | 18 – 26.5 |
| DIN Rail Mounting Type : | TH35-15 | TH35-7.5 |
| Connector Mounting Type : | DIN Rail |
| Housing Material : | Polyamide |
| Wire Size (AWG): | 2 |
| Wire Size (mm2): | 35 |
| Tool Size - Main Circuit : | 4 mm [ .157 in ] |
| Wire Stripping Length - Output 2 : | 11 mm [ .43 in ] |
| Product Height : | 75 mm [ 2.645 in ] |
| Main Circuit Capacity - 1 Insulated Ferrule per Screw Clamp (mm2): | 10 – 35 |
| Wire Stripping Length - Output 1 : | 11 mm [ .43 in ] |
| Main Circuit Capacity - 1 Insulated Ferrule per Screw Clamp (AWG): | 8 – 2 |
| Main Circuit Capacity - 1 Rigid Stranded Conductor per Screw Clamp (AWG): | 8 – 2 |
| Main Circuit Capacity - 1 Rigid Stranded Conductor per Screw Clamp (mm2): | 10 – 35 |
| Hole Diameter - Main Circuit : | 9.8 mm [ .386 in ] |
| Hole Diameter - Output 1 : | 6.8 mm [ .267 in ] |
| Hole Diameter - Output 2 : | 6.5 mm [ .256 in ] |
| Product Spacing : | 28.2 mm [ 1.11 in ] |
| Output 1 Capacity - 1 Insulated Ferrule (AWG): | 14 – 6 |
| Tool Size - Output 2 : | 5.5 mm [ .217 in ] |
| Output 1 Capacity - 1 Insulated Ferrule (mm2): | 2.5 – 16 |
| Wire Stripping Length - Main Circuit : | 15 mm [ .591 in ] |
| Output 2 Capacity - 1 Insulated Ferrule (AWG): | 14 – 6 |
| Tool Size - Output 1 : | 3 mm [ .118 in ] |
| Output 2 Capacity - 1 Insulated Ferrule (mm2): | 2.5 – 16 |
| Output 1 Capacity - 1 Rigid Stranded Conductor (AWG): | 10 – 6 |
| Output 1 Capacity - 1 Rigid Stranded Conductor (mm2): | 6 – 16 |
| Output 2 Capacity - 1 Rigid Stranded Conductor (AWG): | 14 – 6 |
| Output 2 Capacity - 1 Rigid Stranded Conductor (mm2): | 2.5 – 16 |
| Installation Temperature Range : | -5 – 40 °C [ 23 – 104 °F ] |
| Operating Temperature Range : | -55 – 110 °C [ -67 – 230 °F ] |
| UL Flammability Rating : | UL 94V-0 |
| Tool - Output 1 : | Allen Key |
| Tool - Output 2 : | Positive Drive Flat Screwdriver |
| Tool - Main Circuit : | Allen Key |
| IP Rating : | IP20 |