Function: Communication using the DNP3 protocol can be conveniently parameterized with the configurator. To enable this, the CODESYS V3 development environment must be extended once with the WAGO Telecontrol Package. This license activates the DNP3 protocol on the slave side. The configurator fully supports the DNP3-specific functions of all WAGO telecontrollers. The configurator sets up DNP3 objects while configuring data exchange to the PLC application or I/O modules. Settings can be imported and exported in the DNP3 XML Device Profile format. WAGO's telecontrollers can operate as DNP3 slaves via TCP, UDP, or serial communication. Cyclical time synchronization of the telecontrol substation (slave) can be performed by the master according to DNP3 Device Profile 1.7.2. In the monitoring direction, the WAGO DNP3 Slave can send digital, analog and count values to the master. Both digital and analog values can be received in the control direction. Analog values can be processed in 16-bit, 32-bit or FLOAT format. Count values can be processed in 16-bit or 32-bit format. Key Benefits: Use the PFC200 Controller as a telecontrol substation (slave) in a DNP3 control system (master) via TCP, UDP, or serial Create a gateway application to transfer data, e.g., from Modbus® field devices to a DNP3 control system Usage: The license is registered via WAGO Upload and loaded onto a device. No further installation steps are required. Technical Data: See the document “Runtime; DNP3 Slave Device Profile” at www.wago.com.